• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

Section 443 Fixed Guideway Transit and Passenger Rail Systems [SFM]

California Building Code 2016 (Vol 1 & 2) > 4 Special Detailed Requirements Based on Use and Occupancy > 443 Fixed Guideway Transit and Passenger Rail Systems [SFM]
JUMP TO FULL CODE CHAPTER

443.1 General

443.1.1 Scope

The provisions of this section and NFPA 130 shall apply to buildings or structures defined as stations for fixed guideway transit and passenger rail systems and shall supersede other similar requirements in other sections of this code.
Note: See Chapter 35 for California Amendments to NFPA 130.

443.2 Special Provisions

443.2.1 Automatic Sprinkler System

See Section 903.2.17.1.

443.2.2 Station Guideway Deluge System

See Section 903.2.17.2.

443.2.3 Standpipe Systems

See Section 905.3.11.

443.2.4 Fire Alarm and Communication Systems

See Section 907.2.26.

443.2.5 Emergency Ventilation Control

Emergency ventilation systems shall comply with this section and NFPA 130.

443.2.5.1

Emergency ventilation systems shall be supervised and/or controlled in all operating modes locally (motor control center and/or fan unit) and remotely at both the Operations Control Center and the station Fire Command Center.

443.2.5.2

Fan running shall be provided by sensing devices for each fan for operation in both the supply and exhaust directions.

443.2.5.3

Trouble status signals shall be annunciated in the local control room. A summarized trouble signal shall be annunciated at Operations Control Center and Fire Command Center.

Related Code Sections


Section 443 Special Detailed Requirements Based on Use and Occupancy, Fixed Guideway Transit and Passenger Rail Systems [SFM]
The provisions of this section and NFPA 130 shall apply to buildings or structures defined as stations for fixed guideway transit and passenger rail ...
California Building Code 2016 (Vol 1 & 2) > 4 Special Detailed Requirements Based on Use and Occupancy > 443 Fixed Guideway Transit and Passenger Rail Systems [SFM]
Section 443 Special Detailed Requirements Based on Occupancy and Use, Fixed Guideway Transit and Passenger Rail Systems [SFM]
The provisions of this section and NFPA 130 shall apply to buildings or structures defined as stations for fixed guideway transit and passenger rail ...
California Building Code 2019 (Vol 1 & 2) > 4 Special Detailed Requirements Based on Occupancy and Use > 443 Fixed Guideway Transit and Passenger Rail Systems [SFM]
443.2.1 Special Detailed Requirements Based on Use and Occupancy, Automatic Sprinkler System
See Section 903.2.17.1 ...
California Building Code 2016 (Vol 1 & 2) > 4 Special Detailed Requirements Based on Use and Occupancy > 443 Fixed Guideway Transit and Passenger Rail Systems [SFM] > 443.2 Special Provisions > 443.2.1 Automatic Sprinkler System
443.2.4 Special Detailed Requirements Based on Use and Occupancy, Fire Alarm and Communication Systems
See Section 907.2.26 ...
California Building Code 2016 (Vol 1 & 2) > 4 Special Detailed Requirements Based on Use and Occupancy > 443 Fixed Guideway Transit and Passenger Rail Systems [SFM] > 443.2 Special Provisions > 443.2.4 Fire Alarm and Communication Systems
443.2.5 Special Detailed Requirements Based on Use and Occupancy, Emergency Ventilation Control
Emergency ventilation systems shall comply with this section and NFPA 130 ...
California Building Code 2016 (Vol 1 & 2) > 4 Special Detailed Requirements Based on Use and Occupancy > 443 Fixed Guideway Transit and Passenger Rail Systems [SFM] > 443.2 Special Provisions > 443.2.5 Emergency Ventilation Control
Help Contact Us Privacy Terms
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING