// CODE SNIPPET
904.3.7.2.5 Fixed Emergency Forced Ventilation
Go To Full Code Chapter
When the protected area is normally occupied, a fixed emergency forced ventilation system sufficient to accomplish at least six air changes per hour of the flooded protected area shall be provided unless all of the following apply:
- The clean agent fire extinguishing system is used to extinguish a Class A fire.
- The design concentration does not exceed the "no observable adverse effect level" for halocarbon agents, or "no effect level" for inert gas agents as defined in NFPA 2001, as modified by FC Appendix B.
- If other than inert gas agents are used, the quantity of the thermal decomposition products formed from such agents is below the dangerous toxic load (DTL) for humans as described in Meldrum's "Toxicology of Substances in Relation to Major Hazards: Hydrogen Fluoride" (HMSO, London, 1993). Upon request, documentation of hazard assessment of thermal decomposition products formed from such agents shall be filed with the department.
Related Code Sections
2.14.2.3 Electric Elevators, Ventilation
opening provided by forced ventilation systems shall be permitted to be part of the natural ventilation area on the part of the car in which it is located ...
G.3.2 High Pressure Natural Gas Installations, Emergency Ventilation
An emergency ventilation system shall be provided in accordance with NFPA 69 and shall be approved by the Fire Department. Ventilation calculations ...
G.3.2 High Pressure Natural Gas Installations, Emergency Ventilation
An emergency ventilation system shall be provided in accordance with NFPA 69 and shall be approved by the Fire Department. Ventilation calculations ...
§27-838 Heating and Combustion Equipment, Ventilation
Fixed ventilation for combustion air to the incinerator room shall be provided by a louvered opening in a wall to outdoor air. When ducts are used ...
Article 6 Ventilation [PDF] (page 3)
surface of at least three square feet and arranged so as to provide fixed ventilating openings of at least one and onehalf square feet to the outer air ...