All spaces between fireplaces and floors and ceilings through which fireplaces pass shall be fireblocked with noncombustible material securely fastened in place. The fireblocking of spaces between wood joists, beams or headers shall be to a depth of 1 inch (25 mm) and shall only be placed on strips of metal or metal lath laid across the spaces between combustible material and the chimney.

Related Code Sections

2111.13 Masonry, Fireplace Fireblocking
All spaces between fireplaces and floors and ceilings through which fireplaces pass shall be fireblocked with noncombustible material securely ...
2111.13 Masonry, Fireplace Fireblocking
All spaces between fireplaces and floors and ceilings through which fireplaces pass shall be fireblocked with noncombustible material securely ...
2111.12 Masonry, Fireplace Clearance
of masonry fireplaces. The airspace shall not be filled, except to provide fireblocking in accordance with Section 2111.13. Exceptions ...