708.4.2 Fireblocks and Draftstops in Combustible Construction
JUMP TO FULL CODE CHAPTER
In combustible construction where fire partitions do not extend to the underside of the floor or roof sheathing, deck or slab above, the space above and along the line of the fire partition shall be provided with one of the following:
- Fireblocking up to the underside of the floor or roof sheathing, deck or slab above using materials complying with Section 718.2.1.
- Draftstopping up to the underside of the floor or roof sheathing, deck or slab above using materials complying with Section 718.3.1 for floors or Section 718.4.1 for attics.
Exceptions:
- Buildings equipped with an automatic sprinkler system installed throughout in accordance with Section 903.3.1.1, or in accordance with Section 903.3.1.2 provided that protection is provided in the space between the top of the fire partition and underside of the floor or roof sheathing, deck or slab above as required for systems complying with Section 903.3.1.1.
- Where corridor walls provide a sleeping unit or dwelling unit separation, draftstopping shall only be required above one of the corridor walls.
- In Group R-2 occupancies with fewer than four dwelling units, fireblocking and draftstopping shall not be required.
- In Group R-2 occupancies up to and including four stories in height in buildings not exceeding 60 feet (18 288 mm) in height above grade plane, the attic space shall be subdivided by draftstops into areas not exceeding 3,000 square feet (279 m2) or above every two dwelling units, whichever is smaller.
- In Group R-3 occupancies with fewer than three dwelling units, fire-blocking and draftstopping shall not be required in floor assemblies.
Related Code Sections
708.4.2 Fire and Smoke Protection Features, Fireblocks and Draftstops in Combustible Construction
In combustible construction where fire partitions do not extend to the underside of the floor or roof sheathing, deck or slab above, the space ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 708 Fire Partitions > 708.4 Continuity > 708.4.2 Fireblocks and Draftstops in Combustible Construction
708.4.2 Fire and Smoke Protection Features, Fireblocks and Draftstops in Combustible Construction
In combustible construction where fire partitions do not extend to the underside of the floor or roof sheathing, deck or slab above, the space ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 708 Fire Partitions > 708.4 Continuity > 708.4.2 Fireblocks and Draftstops in Combustible Construction
718.1 Fire and Smoke Protection Features, General
Fireblocking and draftstopping shall be installed in combustible concealed locations in accordance with this section. Fireblocking shall comply ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 718 Concealed Spaces > 718.1 General
718.1 Fire and Smoke Protection Features, General
Fireblocking and draftstopping shall be installed in combustible concealed locations in accordance with this section. Fireblocking shall comply ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 718 Concealed Spaces > 718.1 General
718.2 Fire and Smoke Protection Features, Fireblocking
In combustible construction, fireblocking shall be installed to cut off concealed draft openings (both vertical and horizontal) and shall form ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 718 Concealed Spaces > 718.2 Fireblocking