// CODE SNIPPET

907.3 Fire Safety Functions

Building Code 2015 of Utah > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.3 Fire Safety Functions
JUMP TO FULL CODE CHAPTER
Automatic fire detectors utilized for the purpose of performing fire safety functions shall be connected to the building's fire alarm control unit where a fire alarm system is required by Section 907.2. Detectors shall, upon actuation, perform the intended function and activate the alarm notification appliances or activate a visible and audible supervisory signal at a constantly attended location. In buildings not equipped with a fire alarm system, the automatic fire detector shall be powered by normal electrical service and, upon actuation, perform the intended function. The detectors shall be located in accordance with NFPA 72.

907.3.1 Duct Smoke Detectors

Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. In facilities that are required to be monitored by a supervising station, duct smoke detectors shall report only as a supervisory signal and not as a fire alarm. They shall not be used as a substitute for required open area detection.

Exceptions:

1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building's alarm notification appliances.

2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.

907.3.2 Delayed Egress Locks

Where delayed egress locks are installed on means of egress doors in accordance with Section 1010.1.9.7, an automatic smoke or heat detection system shall be installed as required by that section.

907.3.3 Elevator Emergency Operation

Automatic fire detectors installed for elevator emergency operation shall be installed in accordance with the provisions of ASME A17.1/CSA B44 and NFPA 72.

907.3.4 Wiring

The wiring to the auxiliary devices and equipment used to accomplish the fire safety functions shall be monitored for integrity in accordance with NFPA 72.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


907.3 Fire Protection Systems, Fire Safety Functions
Automatic fire detectors utilized for the purpose of performing fire safety functions shall be connected to the building's fire alarm control unit ...
Building Code 2015 of Utah > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.3 Fire Safety Functions
907.3 Fire Protection and Life Safety Systems, Fire safety functions
Automatic fire detectors utilized for the purpose of performing fire safety functions shall be connected to the building’s fire alarm control unit ...
Building Code 2018 of Utah > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.3 Fire safety functions
907.3.1 Fire Protection Systems, Duct Smoke Detectors
initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function ...
Building Code 2015 of Utah > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.3 Fire Safety Functions > 907.3.1 Duct Smoke Detectors
907.3.2 Fire Protection Systems, Delayed Egress Locks
Where delayed egress locks are installed on means of egress doors in accordance with Section 1010.1.9.7, an automatic smoke or heat detection system ...
Building Code 2015 of Utah > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.3 Fire Safety Functions > 907.3.2 Delayed Egress Locks
907.3.3 Fire Protection Systems, Elevator Emergency Operation
Automatic fire detectors installed for elevator emergency operation shall be installed in accordance with the provisions of ASME A17.1/CSA B44 ...
Building Code 2015 of Utah > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.3 Fire Safety Functions > 907.3.3 Elevator Emergency Operation
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US