715.6 Fire-Resistant Joint Systems in Smoke Barriers
JUMP TO FULL CODE CHAPTER
Fire-resistant joint systems in smoke barriers, and joints at the intersection of a horizontal smoke barrier and an exterior curtain wall, shall be tested in accordance with the requirements of UL 2079 for air leakage. The L rating of the joint system shall not exceed 5 cfm per linear foot (0.00775 m3/s m) of joint at 0.30 inch (7.47 Pa) of water for both the ambient temperature and elevated temperature tests.
Related Code Sections
713.6 Fire-Resistance-Rated Construction, Fire-Resistant Joint Systems in Smoke Barriers
Fire-resistant joint systems in smoke barriers shall be tested in accordance with the requirements of UL 2079 for air leakage. The air leakage rate ...
2010 Building Code of NY > 7 Fire-Resistance-Rated Construction > 713 Fire-Resistant Joint Systems > 713.6 Fire-Resistant Joint Systems in Smoke Barriers
715.6 Fire and Smoke Protection Features, Fire-Resistant Joint Systems in Smoke Barriers
Fire-resistant joint systems in smoke barriers , and joints at the intersection of a horizontal smoke barrier and an exterior curtain wall, shall ...
Building Code 2015 of New York State > 7 Fire and Smoke Protection Features > 715 Fire-Resistant Joint Systems > 715.6 Fire-Resistant Joint Systems in Smoke Barriers
715.6 Fire and Smoke Protection Features, Fire-Resistant Joint Systems in Smoke Barriers
Fire-resistant joint systems in smoke barriers , and joints at the intersection of a horizontal smoke barrier and an exterior curtain wall, shall ...
2020 Building Code of New York State > 7 Fire and Smoke Protection Features > 715 Fire-Resistant Joint Systems > 715.6 Fire-Resistant Joint Systems in Smoke Barriers
Section 702 Fire and Smoke Protection Features, Definitions
The following terms are defined in Chapter 2: DRAFTSTOP. FIREBLOCKING. FIRE-RESISTANT JOINT SYSTEM. MEMBRANE-PENETRATION FIRESTOP SYSTEM ...
703.1 Fire-Resistance-Rated Construction, Maintenance
The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers ...
2010 Fire Code of NY > 7 Fire-Resistance-Rated Construction > 703 Fire-Resistance-Rated Construction > 703.1 Maintenance