• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

402.4.2 Fire-Resistance-Rated Separation

Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 402 Covered Mall and Open Mall Buildings > 402.4 Construction > 402.4.2 Fire-Resistance-Rated Separation
JUMP TO FULL CODE CHAPTER
Fire-resistance-rated separation is not required between tenant spaces and the mall. Fire-resistance-rated separation is not required between a food court and adjacent tenant spaces or the mall.

402.4.2.1 Tenant Separations

Each tenant space shall be separated from other tenant spaces by a fire partition complying with Section 708. A tenant separation wall is not required between any tenant space and the mall.

402.4.2.2 Anchor Building Separation

ILLUSTRATION
CALCULATE P
P Premium Feature

This feature is included in premium subscriptions only. Click below to start a free trial.

Try 2 Weeks Free
CALCULATE
Calculate code sheet portions referencing this topic.
An anchor building shall be separated from the covered or open mall building by fire walls complying with Section 706.
Exceptions:
  1. Anchor buildings of not more than three stories above grade plane that have an occupancy classification the same as that permitted for tenants of the mall building shall be separated by 2-hour fire-resistance-rated fire barriers complying with Section 707.
  2. The exterior walls of anchor buildings separated from an open mall building by an open mall shall comply with Table 602.

402.4.2.2.1 Openings Between Anchor Building and Mall

Except for the separation between Group R-1 sleeping units and the mall, openings between anchor buildings of Type IA, IB, IIA or IIB construction and the mall need not be protected.

402.4.2.3 Parking Garages

An attached garage for the storage of passenger vehicles having a capacity of not more than nine persons and open parking garages shall be considered as a separate building where it is separated from the covered or open mall building or anchor building by not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both.
Parking garages, which are separated from covered mall buildings, open mall buildings or anchor buildings, shall comply with the provisions of Table 602.
Pedestrian walkways and tunnels that connect garages to mall buildings or anchor buildings shall be constructed in accordance with Section 3104.

Related Code Sections


402.4.2 Special Detailed Requirements Based on Occupancy and Use, Fire-Resistance-Rated Separation
Fire-resistance-rated separation is not required between tenant spaces and the mall . Fire-resistance-rated separation is not required between ...
Building Code 2021 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 402 Covered Mall and Open Mall Buildings > 402.4 Construction > 402.4.2 Fire-Resistance-Rated Separation
402.4.2 Special Detailed Requirements Based on Occupancy and Use, Fire-Resistance-Rated Separation
Fire-resistance-rated separation is not required between tenant spaces and the mall . Fire-resistance-rated separation is not required between ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 402 Covered Mall and Open Mall Buildings > 402.4 Construction > 402.4.2 Fire-Resistance-Rated Separation
402.4.2.3 Special Detailed Requirements Based on Occupancy and Use, Parking Garages
be considered as a separate building where it is separated from the covered or open mall building or anchor building by not less than 2-hour fire barriers ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 402 Covered Mall and Open Mall Buildings > 402.4 Construction > 402.4.2 Fire-Resistance-Rated Separation > 402.4.2.3 Parking Garages
402.4.2.2.1 Special Detailed Requirements Based on Occupancy and Use, Openings Between Anchor Building and Mall
Except for the separation between Group R-1 sleeping units and the mall , openings between anchor buildings of Type IA, IB, IIA or IIB ...
Building Code 2021 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 402 Covered Mall and Open Mall Buildings > 402.4 Construction > 402.4.2 Fire-Resistance-Rated Separation > 402.4.2.2 Anchor Building Separation > 402.4.2.2.1 Openings Between Anchor Building and Mall
402.4.2.2.1 Special Detailed Requirements Based on Occupancy and Use, Openings Between Anchor Building and Mall
Except for the separation between Group R-1 sleeping units and the mall , openings between anchor buildings of Type IA, IB, IIA or IIB ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 402 Covered Mall and Open Mall Buildings > 402.4 Construction > 402.4.2 Fire-Resistance-Rated Separation > 402.4.2.2 Anchor Building Separation > 402.4.2.2.1 Openings Between Anchor Building and Mall
Help Contact Us Privacy Terms
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING