Section 913 Fire Pumps
JUMP TO FULL CODE CHAPTER
Where provided or required, fire pumps shall be installed in accordance with this section, NFPA 20, Appendix Q and other applicable sections of this code.
The fire pump, driver and controller shall be protected in accordance with NFPA 20 against possible interruption of service.
Fire pumps shall be located in rooms that are separated from all other areas of the building by 2-hour fire barriers constructed in accordance with Section 707 or 2-hour horizontal assemblies constructed in accordance with Section 712, or both.
Exceptions:
- In other than high-rise buildings, separation by 1-hour fire barriers constructed in accordance with Section 707 or 1-hour horizontal assemblies constructed in accordance with Section 712, or both, shall be permitted in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
- Separation is not required for fire pumps physically separated in accordance with NFPA 20.
- Separation is not required for a fire pump, other than an automatic standpipe fire pump, where such fire pump is located in a mechanical equipment room enclosed by 2-hour fire barriers constructed in accordance with Section 707 or 2-hour horizontal assemblies constructed in accordance with Section 712, or both.
Suitable means shall be provided for maintaining the temperature of a pump room or pump house, where required, above 40°F (5°C).
Temperature of the pump room, pump house or area where engines are installed shall never be less than the minimum recommended by the engine manufacturer. The engine manufacturer's recommendations for oil heaters shall be followed.
Where provided, the fire pump suction, discharge and bypass valves, and isolation valves on the backflow prevention device or assembly shall be supervised open as required by Section 907.
Fire pump test outlet control valves shall be supervised in the closed position. Individual hose valves on the test header are not required to be monitored.
Acceptance testing shall be done in accordance with the requirements of the New York City Fire Code and NFPA 20. Refurbished or repaired fire pumps shall be tested in accordance with the New York City Fire Code and NFPA 20.
Related Code Sections
Section 913 Fire Protection Systems, Fire Pumps
Where provided or required, fire pumps shall be installed in accordance with this section, NFPA 20, Appendix Q and other applicable sections ...
§27-946 Fire Alarm, Detection and Extinguishing Equipment, Fire Pumps
supply to the standpipe system shall be supplemented by one or more manually operated fire pumps as follows: (1) Standpipe systems in buildings more ...
NYC 1968 Code (Vol I) > 17 Fire Alarm, Detection and Extinguishing Equipment > 3 Standpipe Requirements > §27-946 Fire Pumps
2702.1.4 Electrical, Protection of Fire Pumps
Where electrically powered fire pumps are connected to the emergency power system, overcurrent protection and feeder conductors shall be provided ...
NYC Building Code 2014 > 27 Electrical > 2702 Emergency and Standby Power Systems > 2702.1 Installation > 2702.1.4 Protection of Fire Pumps
Section Q106 Modified National Standards for Automatic Sprinkler, Standpipe, Fire Pump and Fire Alarm Systems, Installation of Stationary Fire Pumps
Fire pumps, systems, where required by this code, shall be installed in accordance with NFPA 20, Standard for the Installation of Stationary Fire ...
NYC Building Code 2014 > Q Modified National Standards for Automatic Sprinkler, Standpipe, Fire Pump and Fire Alarm Systems > Q106 Installation of Stationary Fire Pumps
403.3.2 Special Detailed Requirements Based on Use and Occupancy, Water Supply to Required Fire Pumps
Required fire pumps shall be provided with water supplies in accordance with Section 905.2 and NFPA 14 as modified by Appendix Q ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 403 High-Rise Buildings > 403.3 Automatic Sprinkler System > 403.3.2 Water Supply to Required Fire Pumps