913.6 Fire Pump Supervision
JUMP TO FULL CODE CHAPTER
The following fire pump operations shall be electrically supervised by the fire alarm system in accordance with the Electrical Code and NFPA 20; and monitored by a central station in accordance with this code and the rules:
- Pump running.
- Pump power failed.
- Pump phase reversal.
Related Code Sections
913.4.1 Fire Protection Systems, Test Outlet Control Valve Supervision
Fire pump test outlet control valves shall be supervised in the closed position. Individual hose valves on the test header are not required ...
NYC Building Code 2014 > 9 Fire Protection Systems > 913 Fire Pumps > 913.4 Valve Supervision > 913.4.1 Test Outlet Control Valve Supervision
913.4.1 Fire Protection Systems, Test Outlet Control Valve Supervision
Fire pump test outlet control valves shall be supervised in the closed position. Individual hose valves on the test header are not required ...
NYC Building Code 2022 > 9 Fire Protection Systems > 913 Fire Pumps > 913.4 Valve Supervision > 913.4.1 Test Outlet Control Valve Supervision
911.1 Fire Protection Systems, Features
to the public telephone system. 11. Fire pump status indicators. 12. Generator supervision devices, manual start ...
24.2.3.1 Water Supplies, Combined Use
In light hazard occupancies with only limited ordinary hazard areas, an automatic fire pump serving the lower 300 feet (91 440 mm) of the standpipe ...
Standard for the Installation of Sprinkler Systems 2016 of New York City > 24 Water Supplies > 24.2 Types > 24.2.3* Pumps > 24.2.3.1 Combined Use
24.2.3.2 Water Supplies,
fire pump. The pump shall be sized to satisfy the water supply requirements of this section and the New York City Building Code and shall be arranged ...
Standard for the Installation of Sprinkler Systems 2016 of New York City > 24 Water Supplies > 24.2 Types > 24.2.3* Pumps > 24.2.3.2