66.16.6.6 Fire Protection System Design Scheme "F."
JUMP TO FULL CODE CHAPTER
In-rack sprinklers shall meet the following requirements:

FIGURE 66.16.6.6.1(a) Single-Row Rack Sprinkler Layout for Design Scheme "F." [30:16.6.6.1(a)]
FIGURE 66.16.6.6.1(b) Double-Row Rack Sprinkler Layout for Design Scheme "F." (Multiple row racks shall extend the same sprinkler pattern through the rack.) [30:16.6.6.1(b)]
- In-rack sprinklers shall be ordinary temperature-rated, quick-response sprinklers.
- In-rack sprinklers shall have a K-factor of 8.0 (115) or 11.2 (160).
- In-rack sprinklers shall be installed on 20 ft (6 m) vertical increments in accordance with Figure 66.16.6.6.1(a) and Figure 66.16.6.6.1(b) with the in-rack pattern shown in Figure 66.16.6.6.1 (b) repeated from rack face to rack face for multiple-row racks.
- In-rack sprinklers shall provide a minimum discharge flow of 30 gpm (110 L/min) out of the hydraulically most remote sprinkler as follows:


FIGURE 66.16.6.6.1(b) Double-Row Rack Sprinkler Layout for Design Scheme "F." (Multiple row racks shall extend the same sprinkler pattern through the rack.) [30:16.6.6.1(b)]
If there are adjacent bays of rack storage that are
not dedicated to ignitible (flammable or combustible) liquid
storage, the in-rack sprinkler protection shall be extended at
least 8 ft (2.4 m) beyond the area devoted to ignitible (flammable or combustible) liquid storage. [30:16.6.6.2]
The ceiling and in-rack sprinkler demands shall be
balanced at the point of connection to the water supply.
[30:16.6.6.3]
A 500 gpm (1890L/min) hose stream allowance
shall be provided. [30:16.6.6.4]
A 1-hour duration shall be provided for the fire
protection water demand. [30:16.6.6.5]
Related Code Sections
66.16.6 Flammable and Combustible Liquids, Fire Protection System Design Schemes
-Row Rack Sprinkler Layout for Design Scheme "F." [30:16.6.6.1(a)]
FIGURE 66.16.6.6.1(b) Double-Row Rack Sprinkler Layout for Design ...
Fire Code 2021 of Delaware > 66 Flammable and Combustible Liquids > 66.16 Automatic Fire Protection for Inside Liquid Storage Areas > 66.16.6 Fire Protection System Design Schemes
66.16.6 Flammable and Combustible Liquids, Fire Protection System Design Schemes
66.16.6.1.1(a) Single-Row Rack Sprinkler Layout for Design Scheme "A." [30: Figure 16.6.1.1(a)] FIGURE 66.16.6.1.1(b) Double-Row Rack Sprinkler ...
Fire Code 2015 of Delaware > 66 Flammable and Combustible Liquids > 66.16 Automatic Fire Protection for Inside Liquid Storage Areas > 66.16.6 Fire Protection System Design Schemes
66.16.6.6.3 Flammable and Combustible Liquids,
The ceiling and in-rack sprinkler demands shall be
balanced at the point of connection to the water supply.
[ 30: 16.6.6.3 ...
Fire Code 2021 of Delaware > 66 Flammable and Combustible Liquids > 66.16 Automatic Fire Protection for Inside Liquid Storage Areas > 66.16.6 Fire Protection System Design Schemes > 66.16.6.6 Fire Protection System Design Scheme "F." > 66.16.6.6.3
66.16.6.6.4 Flammable and Combustible Liquids,
A 500 gpm (1890L/min) hose stream allowance
shall be provided. [ 30: 16.6.6.4 ...
Fire Code 2021 of Delaware > 66 Flammable and Combustible Liquids > 66.16 Automatic Fire Protection for Inside Liquid Storage Areas > 66.16.6 Fire Protection System Design Schemes > 66.16.6.6 Fire Protection System Design Scheme "F." > 66.16.6.6.4
66.16.6.6.5 Flammable and Combustible Liquids,
A 1-hour duration shall be provided for the fire
protection water demand. [ 30: 16.6.6.5] ...