2210.5 Fire Prevention Regulations
JUMP TO FULL CODE CHAPTER
General fire safety regulations for marine motor fuel-dispensing facilities shall comply with Sections 2210.5.1 through 2210.5.7.
Marine motor fuel-dispensing facilities shall be maintained in a neat and orderly manner. Accumulations of rubbish or waste oils in excessive amounts shall be prohibited.
Spills of Class I, II or IIIA liquids at or on the water shall be reported immediately to the fire department and jurisdictional authorities.
Metal containers with tight-fitting or self-closing metal lids shall be provided for the temporary storage of combustible trash or rubbish.
Vessels or craft shall not be made fast to fuel docks serving other vessels or craft occupying a berth at a marine motor fuel-dispensing facility.
Construction, maintenance, repair and reconditioning work involving the use of open flames, arcs or spark-producing devices shall not be performed at marine motor fuel-dispensing facilities or within 50 feet (15 240 mm) of the dispensing facilities, including piers, wharves or floats, except for emergency repair work approved in writing by the fire code official. Fueling shall not be conducted at the pier, wharf or float during the course of such emergency repairs.
Smoking or open flames shall be prohibited within 50 feet (15 240 mm) of fueling operations. "No Smoking" signs complying with Section 310 shall be posted conspicuously about the premises. Such signs shall have letters not less than 4 inches (102 mm) in height on a background of contrasting color.
Warning signs shall be prominently displayed at the face of each wharf, pier or float at such elevation as to be clearly visible from the decks of marine craft being fueled. Such signs shall have letters not less than 3 inches (76 mm) in height on a background of contrasting color bearing the following or approved equivalent wording:
WARNING
NO SMOKING—STOP ENGINE WHILE FUELING, SHUT OFF ELECTRICITY.
DO NOT START ENGINE UNTIL AFTER BELOW
DECK SPACES ARE VENTILATED.
Related Code Sections
2210.5 Motor Fuel-Dispensing Facilities and Repair Garages, Fire Prevention Regulations
General fire safety regulations for marine motor fuel-dispensing facilities shall comply with Sections 2210.5.1 through 2210.5.7 ...
Fire Code 2009 of Alabama > 22 Motor Fuel-Dispensing Facilities and Repair Garages > 2210 Marine Motor Fuel-Dispensing Facilities > 2210.5 Fire Prevention Regulations
2310.5 Motor Fuel-Dispensing Facilities and Repair Garages, Fire Prevention Regulations
General fire safety regulations for marine motor fuel-dispensing facilities shall comply with Sections 2310.5.1 through 2310.5.7 ...
Fire Code 2015 of Alabama > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2310 Marine Motor Fuel-Dispensing Facilities > 2310.5 Fire Prevention Regulations
2210.5.5 Motor Fuel-Dispensing Facilities and Repair Garages, Sources of Ignition
for emergency repair work approved in writing by the fire code official . Fueling shall not be conducted at the pier, wharf or float during the course ...
Fire Code 2009 of Alabama > 22 Motor Fuel-Dispensing Facilities and Repair Garages > 2210 Marine Motor Fuel-Dispensing Facilities > 2210.5 Fire Prevention Regulations > 2210.5.5 Sources of Ignition
2210.5.6 Motor Fuel-Dispensing Facilities and Repair Garages, Preparation of Tanks for Fueling
Boat owners and operators shall not offer their craft for fueling unless the tanks being filled are properly vented to dissipate fumes ...
Fire Code 2009 of Alabama > 22 Motor Fuel-Dispensing Facilities and Repair Garages > 2210 Marine Motor Fuel-Dispensing Facilities > 2210.5 Fire Prevention Regulations > 2210.5.6 Preparation of Tanks for Fueling
2210.5.7 Motor Fuel-Dispensing Facilities and Repair Garages, Warning Signs
Warning signs shall be prominently displayed at the face of each wharf, pier or float at such elevation as to be clearly visible from the decks ...