3109F.7 Fire Piping and Pipeline Systems
JUMP TO FULL CODE CHAPTER
Firewater and foam piping and fittings shall meet the following requirements:
- Conform to NFPA 11 [9.14], NFPA 24 [9.15], and ASME B16.5 [9.16] (N/E).
- Fire mains shall be carbon steel pipe (N/E).
- High density polyethylene (HDPE) piping may be used for buried pipelines (N/E).
- Piping and appurtenances shall be color-coded per local jurisdiction requirements or per ASME A13.1 [9.17] (N/E).
- Pipeline stress analysis shall be performed for firewater pipelines per Section 3109F.3 (N).
- External visual inspection shall be performed per Section 3102F.3.5.5 (N/E).
Related Code Sections
3109F.7 [SLC] Marine Oil Terminals, Fire Piping and Pipeline Systems
). Fire mains shall be carbon steel pipe (N/E). High density polyethylene (HDPE) piping may be used for buried pipelines (N/E). Piping ...
Los Angeles Building Code > 31F [SLC] Marine Oil Terminals > 3109F Piping and Pipelines > 3109F.7 Fire Piping and Pipeline Systems
3101F.8.3 [SLC] Marine Oil Terminals, Division Review
, analysis or evaluation of MOTs. Any significant change, modification or re-design of a structural, mooring, fire, piping/pipelines, mechanical ...
Los Angeles Building Code > 31F [SLC] Marine Oil Terminals > 3101F [SLC] Introduction > 3101F.8 Review Requirements > 3101F.8.3 Division Review
3102F.3.4.6 [SLC] Marine Oil Terminals, Mechanical Inspection Team
A registered engineer shall direct the on-site team performing the inspection and evaluation of piping/pipeline, mechanical and fire components ...
Los Angeles Building Code > 31F [SLC] Marine Oil Terminals > 3102F Audit and Inspection > 3102F.3 Audits > 3102F.3.4 Audit Team > 3102F.3.4.6 Mechanical Inspection Team
3112F.5 [SLC] Marine Oil Terminals, LNG Pipelines
insulation systems used to support pipe whose stability is essential, shall be resistant to or protected against fire exposure, escaping cold liquid ...
Los Angeles Building Code > 31F [SLC] Marine Oil Terminals > 3112F Requirements Specific to Marine Terminals That Transfer LNG > 3112F.5 LNG Pipelines
3108F.7 [SLC] Marine Oil Terminals, Critical Systems Seismic Assessment (N/E)
Fire detection and protection systems, and emergency shutdown systems shall have a seismic assessment per Section 3104F.6. For firewater piping ...
Los Angeles Building Code > 31F [SLC] Marine Oil Terminals > 3108F Fire Prevention, Detection and Suppression > 3108F.7 Critical Systems Seismic Assessment (N/E)