Section 502 Fire Hazard Severity
JUMP TO FULL CODE CHAPTER
The fire hazard severity of building sites for buildings hereafter constructed, modified or relocated into wildland-urban interface areas shall be established in accordance with Table 502.1. See also Appendix C.
TABLE 502.1 FIRE HAZARD SEVERITY
TABLE 502.1 FIRE HAZARD SEVERITY
FUEL MODELb | CRITICAL FIRE WEATHER FREQUENCY | ||||||||
≤ 1 Daya | 2 to 7 daysa | ≥ 8 daysa | |||||||
Slope (%) | Slope (%) | Slope (%) | |||||||
≤ 40 | 41-60 | ≥ 61 | ≤ 40 | 41-60 | ≥ 61 | ≤ 40 | 41-60 | ≥ 61 | |
Light fuel | M | M | M | M | M | M | M | M | H |
Medium fuel | M | M | H | H | H | H | E | E | E |
Heavy fuel | H | H | H | H | E | E | E | E | E |
E = Extreme hazard; |
H = High hazard; |
M = Moderate hazard. |
a. Days per annum. |
b. Where required by the code official, fuel classification shall be based on the historical fuel type for the area. |
The fire hazard severity identified in Table 502.1 is allowed to be reduced by implementing a vegetation management plan in accordance with Appendix B.
Related Code Sections
Section 502 Special Building Construction Regulations, Fire Hazard Severity
The fire hazard severity of building sites for buildings hereafter constructed, modified or relocated into wildland-urban interface areas shall ...
Wildland-Urban Interface Code 2015 of Pennsylvania > 5 Special Building Construction Regulations > 502 Fire Hazard Severity
Section 502 Special Building Construction Regulations, Fire Hazard Severity
The fire hazard severity of building sites for all buildings hereafter constructed, modified or relocated into wildland-urban interface areas shall ...
Wildland-Urban Interface Code 2009 of Pennsylvania > 5 Special Building Construction Regulations > 502 Fire Hazard Severity
105.2 Scope and Administration, Technical Assistance
management for purposes of establishing fire hazard severity to recommend necessary changes ...
Wildland-Urban Interface Code 2009 of Pennsylvania > 1 Scope and Administration > 105 Compliance Alternatives > 105.2 Technical Assistance
105.2 Scope and Administration, Technical Assistance
, the facilities and appurtenances situated thereon and fuel management for purposes of establishing fire hazard severity to recommend necessary changes ...
Wildland-Urban Interface Code 2015 of Pennsylvania > 1 Scope and Administration > 105 Compliance Alternatives > 105.2 Technical Assistance
503.1 Special Building Construction Regulations, General
IGNITION-RESISTANT CONSTRUCTION a DEFENSIBLE SPACE c FIRE HAZARD SEVERITY Moderate Hazard High Hazard Extreme Hazard ...
Wildland-Urban Interface Code 2015 of Pennsylvania > 5 Special Building Construction Regulations > 503 Ignition-Resistant Construction and Material > 503.1 General