Section B104 Fire-Flow Calculation Area
JUMP TO FULL CODE CHAPTER
The fire-flow calculation area shall be the total floor area of all floor levels within the exterior walls, and under the horizontal projections of the roof of a building, except as modified in Section B104.3.
Portions of buildings that are separated by fire walls without openings, constructed in accordance with the California Building Code, are allowed to be considered as separate fire-flow calculation areas.
The fire-flow calculation area of buildings constructed of Type IA and Type IB construction shall be the area of the three largest successive floors.
Exception: Fire-flow calculation area for open parking garages shall be determined by the area of the largest floor.
Related Code Sections
Section B104 Fire-Flow Requirements for Buildings, Fire-Flow Calculation Area
The fire-flow calculation area shall be the total floor area of all floor levels within the exterior walls, and under the horizontal projections ...
California Fire Code 2019 > B Fire-Flow Requirements for Buildings > B104 Fire-Flow Calculation Area
Section B104 Fire-Flow Requirements for Buildings, Fire-Flow Calculation Area
The fire-flow calculation area shall be the total floor area of all floor levels within the exterior walls, and under the horizontal projections ...
California Fire Code 2016 > B Fire-Flow Requirements for Buildings > B104 Fire-Flow Calculation Area
B104.1 Fire-Flow Requirements for Buildings, General
The fire-flow calculation area shall be the total floor area of all floor levels within the exterior walls, and under the horizontal projections ...
California Fire Code 2016 > B Fire-Flow Requirements for Buildings > B104 Fire-Flow Calculation Area > B104.1 General
Section B102 Fire-Flow Requirements for Buildings, Definitions
square inch (psi) (138 kPa) residual pressure, that is available for fire fighting. FIRE-FLOW CALCULATION AREA. The floor area, in square feet (m ...
Section B102 Fire-Flow Requirements for Buildings, Definitions
square inch (psi) (138 kPa) residual pressure, that is available for fire fighting. FIRE-FLOW CALCULATION AREA. The floor area, in square feet (m ...