// CODE SNIPPET

909.16 Fire Fighter's Smoke Control Panel

Building Code 2015 of Utah > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.16 Fire Fighter's Smoke Control Panel
JUMP TO FULL CODE CHAPTER
A fire fighter's smoke control panel for fire department emergency response purposes only shall be provided and shall include manual control or override of automatic control for mechanical smoke control systems. The panel shall be located in a fire command center complying with Section 911 in high-rise buildings or buildings with smoke-protected assembly seating. In all other buildings, the fire fighter's smoke control panel shall be installed in an approved location adjacent to the fire alarm control panel. The fire fighter's smoke control panel shall comply with Sections 909.16.1 through 909.16.3.

909.16.1 Smoke Control Systems

Fans within the building shall be shown on the fire fighter's control panel. A clear indication of the direction of airflow and the relationship of components shall be displayed. Status indicators shall be provided for all smoke control equipment, annunciated by fan and zone, and by pilot-lamp-type indicators as follows:

1. Fans, dampers and other operating equipment in their normal status‒WHITE.

2. Fans, dampers and other operating equipment in their off or closed status‒RED.

3. Fans, dampers and other operating equipment in their on or open status‒GREEN.

4. Fans, dampers and other operating equipment in a fault status‒YELLOW/AMBER.

909.16.2 Smoke Control Panel

The fire fighter's control panel shall provide control capability over the complete smoke control system equipment within the building as follows:

1. ON-AUTO-OFF control over each individual piece of operating smoke control equipment that can also be controlled from other sources within the building. This includes stairway pressurization fans; smoke exhaust fans; supply, return and exhaust fans; elevator shaft fans and other operating equipment used or intended for smoke control purposes.

2. OPEN-AUTO-CLOSE control over individual dampers relating to smoke control and that are also controlled from other sources within the building.

3. ON-OFF or OPEN-CLOSE control over smoke control and other critical equipment associated with a fire or smoke emergency and that can only be controlled from the fire fighter's control panel.

Exceptions:

1. Complex systems, where approved, where the controls and indicators are combined to control and indicate all elements of a single smoke zone as a unit.

2. Complex systems, where approved, where the control is accomplished by computer interface using approved, plain English commands.

909.16.3 Control Action and Priorities

The firefighter's control panel actions shall be as follows:

1. ON-OFF and OPEN-CLOSE control actions shall have the highest priority of any control point within the building. Once issued from the fire fighter's control panel, automatic or manual control from any other control point within the building shall not contradict the control action. Where automatic means are provided to interrupt normal, nonemergency equipment operation or produce a specific result to safeguard the building or equipment including, but not limited to, duct freezestats, duct smoke detectors, high-temperature cutouts, temperature-actuated linkage and similar devices, such means shall be capable of being overridden by the fire fighter's control panel. The last control action as indicated by each fire fighter's control panel switch position shall prevail. Control actions shall not require the smoke control system to assume more than one configuration at any one time.

Exception: Power disconnects required by NFPA 70.

2. Only the AUTO position of each three-position firefighter's control panel switch shall allow automatic or manual control action from other control points within the building. The AUTO position shall be the NORMAL, nonemergency, building control position. Where a fire fighter's control panel is in the AUTO position, the actual status of the device (on, off, open, closed) shall continue to be indicated by the status indicator described in Section 909.16.1. Where directed by an automatic signal to assume an emergency condition, the NORMAL position shall become the emergency condition for that device or group of devices within the zone. Control actions shall not require the smoke control system to assume more than one configuration at any one time.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


909.16 Fire Protection Systems, Fire Fighter's Smoke Control Panel
A fire fighter's smoke control panel for fire department emergency response purposes only shall be provided and shall include manual control ...
Building Code 2015 of Utah > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.16 Fire Fighter's Smoke Control Panel
513.16 Exhaust Systems, Fire Fighter's Smoke Control Panel
A fire fighter's smoke control panel for fire department emergency response purposes only shall be provided in accordance with the International ...
Mechanical Code 2015 of Utah > 5 Exhaust Systems > 513 Smoke Control Systems > 513.16 Fire Fighter's Smoke Control Panel
911.1.6 Fire Protection Systems, Required Features
fighter's control panel required by Section 909.16 for smoke control systems installed in the building. Controls for unlocking interior exit stairway ...
Building Code 2015 of Utah > 9 Fire Protection Systems > 911 Fire Command Center > 911.1 General > 911.1.6 Required Features
909.18 Fire Protection Systems, Acceptance Testing
damage. Control sequences shall be verified throughout the system, including verification of override from the fire-fighter's control panel ...
Building Code 2015 of Utah > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.18 Acceptance Testing
909.18.7 Fire Protection Systems, Controls
sequences shall be verified throughout the system, including verification of override from the fire-fighter's control panel and simulation of standby power ...
Building Code 2015 of Utah > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.18 Acceptance Testing > 909.18.7 Controls
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US