2206.8 Fire Extinguishing System for Dispensing Area
JUMP TO FULL CODE CHAPTER
Where flammable liquid motor fuel is dispensed at an automotive liquid motor fuel-dispensing facility, the dispensing area shall be provided with a dry chemical fire extinguishing system designed and installed in accordance with FC904.6, and the following requirements:
- The fire extinguishing system shall be designed to provide overhead protection of the dispenser area encompassed by a circle formed by the fully extended hose and nozzle on each fuel dispenser and both ends of the dispenser island.
- The extinguishing agent containers shall be equipped with indicators to show whether the system is fully charged. Indicators shall be positioned to be easily read from grade.
- The installation, alteration, testing and repair of the fire extinguishing system, including any maintenance or modification of the system, shall be performed by a person possessing a master fire suppression piping contractor license issued by the Department of Buildings and trained and knowledgeable in the installation, operation and maintenance of the specific fire extinguishing system.
- Dispensers shall not be operated when the fire extinguishing system has discharged or is inoperative, except as authorized in writing by the department. The motor fuel-dispensing facility certified attendant shall immediately notify the department of system discharge or inoperability.
- Fire extinguishing systems shall be inspected and tested in accordance with FC2206.9.
- Fire extinguishing systems at fleet automotive liquid motor fuel-dispensing facilities shall be monitored by an approved central station company.
Related Code Sections
G307.4.1.2 Flood-Resistant Construction, Extinguishing System
Fuel-oil storage shall be protected with an alternative automatic fire-extinguishing system complying with Section 904 ...
NYC Building Code 2014 > G Flood-Resistant Construction > G307 Tanks > G307.4 Additional Fuel-Oil Storage Capacity > G307.4.1 Additional Requirements > G307.4.1.2 Extinguishing System
G307.4.1.2 Flood-Resistant Construction, Extinguishing System
Fuel-oil storage shall be protected with an alternative automatic fire-extinguishing system complying with Section 904.
*Section BC G307.4.1.2 ...
NYC Building Code 2008 > G Flood-Resistant Construction > G307 Tanks > G307.4 Additional Fuel-Oil Storage Capacity > G307.4.1 Additional Requirements > G307.4.1.2 Extinguishing System
907.13 Fire Protection Systems, Fire-Extinguishing Systems
Where a fire alarm system is required by another section of this code or is otherwise installed, automatic fire-extinguishing systems shall ...
NYC Building Code 2008 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.13 Fire-Extinguishing Systems
907.4.4 Fire Protection Systems, Fire-Extinguishing Systems
Where a fire alarm system is required by another section of this code or is otherwise installed, automatic fire-extinguishing systems installed ...
NYC Building Code 2014 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.4 Initiating Devices > 907.4.4 Fire-Extinguishing Systems
502.1.2 Exhaust Systems, Fuel-Dispensing Areas
The bottom of an air inlet or exhaust opening in fuel-dispensing areas shall be located not more than 18 inches (457 mm) above the floor ...
NYC Mechanical Code 2008 > 5 Exhaust Systems > 502 Required Systems > 502.1 General > 502.1.2 Fuel-Dispensing Areas