303.1 Where Permitted
Fire escapes shall be permitted only as provided for in Sections 303.1.1 through 303.1.4.
303.1.1 New Buildings
Fire escapes shall not constitute any part of the required means of egress in new buildings.
303.1.2 Existing Fire Escapes
Existing fire escapes shall be continued to be accepted as a component in the means of egress in existing buildings only.
303.1.3 New Fire Escapes
New fire escapes for existing buildings shall be permitted only where exterior stairs cannot be utilized due to lot lines limiting stair size or due to the sidewalks, alleys or roads at grade level. New fire escapes shall not incorporate ladders or access by windows.
303.1.4 Limitations
Fire escapes shall comply with this section and shall not constitute more than 50 percent of the required number of exits nor more than 50 percent of the required exit capacity.
303.2 Location
Where located on the front of the building and where projecting beyond the building line, the lowest landing shall not be less than 7 feet (2134 mm) or more than 12 feet (3658 mm) above grade, and shall be equipped with a counterbalanced stairway to the street. In alleyways and thoroughfares less than 30 feet (9144 mm) wide, the clearance under the lowest landing shall not be less than 12 feet (3658 mm).
303.3 Construction
The fire escape shall be designed to support a live load of 100 pounds per square foot (4788 Pa) and shall be constructed of steel or other approved noncombustible materials. Fire escapes constructed of wood not less than nominal 2 inches (51 mm) thick are permitted on buildings of Type V construction. Walkways and railings located over or supported by combustible roofs in buildings of Type III and IV construction are permitted to be of wood not less than nominal 2 inches (51 mm) thick.
303.4 Dimensions
Stairs shall be at least 22 inches (559 mm) wide with risers not more than, and treads not less than, 8 inches (203 mm) and landings at the foot of stairs not less than 40 inches (1016 mm) wide by 36 inches (914 mm) long, located not more than 8 inches (203 mm) below the door.
303.5 Opening Protectives
Doors and windows along the fire escape shall be protected with 3/4-hour opening protectives.

Related Code Sections

Section 303 Prescriptive Compliance Method, Fire Escapes [B]
Fire escapes shall be permitted only as provided for in Sections 303.1.1 through 303.1.4 ...
303.1.2 Prescriptive Compliance Method, Existing Fire Escapes
Existing fire escapes shall be continued to be accepted as a component in the means of egress in existing buildings only ...
303.1.3 Prescriptive Compliance Method, New Fire Escapes
New fire escapes for existing buildings shall be permitted only where exterior stairs cannot be utilized due to lot lines limiting stair size or due ...
303.1.4 Prescriptive Compliance Method, Limitations
Fire escapes shall comply with this section and shall not constitute more than 50 percent of the required number of exits nor more than 50 percent ...