P2503.5.2 Finished Plumbing
Go To Full Code Chapter
After the plumbing fixtures have been set and their traps filled with water, their connections shall be tested and proved gastight or watertight as follows:
- Watertightness. Each fixture shall be filled and then drained. Traps and fixture connections shall be proven watertight by visual inspection.
-
Gastightness. Where required by the local administrative authority, a final test for gastightness of the DWV system shall be made by the smoke or peppermint test as follows:2.1. Smoke test. Introduce a pungent, thick smoke into the system. When the smoke appears at vent terminals, such terminals shall be sealed and a pressure equivalent to a 1-inch water column (249 Pa) shall be applied and maintained for a test period of not less than 15 minutes.
Related Code Sections
P2503.5.2 Plumbing Administration, Finished Plumbing
After the plumbing fixtures have been set and their traps filled with water, their connections shall be tested and proved gas tight or water tight ...
P2503.5.2 Plumbing Administration, Finished Plumbing
After the plumbing fixtures have been set and their traps filled with water, their connections shall be tested and proved gastight or watertight ...
P2503.5 Plumbing Administration, Drain, Waste and Vent Systems Testing
Rough-in and finished plumbing installations of drain, waste and vent systems shall be tested in accordance with Sections P2503.5.1 and P2503.5.2 ...
714.1 Sanitary Drainage, Sewage Backflow
Where plumbing fixtures are installed on a floor with a finished floor elevation below the elevation of the manhole cover of the next upstream ...
P2603.1 General Plumbing Requirements, General
In the process of installing or repairing any part of a plumbing and drainage installation, the finished floors, walls, ceilings, tile work or any ...