E3406.9 Fine Stranded Conductors
JUMP TO FULL CODE CHAPTER
Connectors and terminals for conductors that are more finely stranded than Class B and Class C stranding as shown in Table E3406.9, shall be identified for the specific conductor class or classes.
CONDUCTOR STRANDINGc
CONDUCTOR SIZE | NUMBER OF STRANDS | |||
Copper | Aluminum | |||
AWG or kcmil | mm2 | Class B | Class C | Class B |
24-30 | 0.20-0.05 | a | — | — |
22 | 0.32 | 7 | — | — |
20 | 0.52 | 10 | — | — |
18 | 0.82 | 16 | — | — |
16 | 1.3 | 26 | — | — |
14-2 | 2.1-33.6 | 7 | 19 | 7b |
1-4/0 | 42.4-107 | 19 | 37 | 19 |
250-500 | 127-253 | 37 | 61 | 37 |
600-1000 | 304-508 | 61 | 91 | 61 |
1250-1500 | 635-759 | 91 | 127 | 91 |
1750-2000 | 886-1016 | 127 | 271 | 127 |
- Number of strands vary.
- Aluminum 14 AWG (2.1 mm2) is not available.
- With the permission of Underwriters Laboratories, Inc., this material is reproduced from UL Standard 486A-B, Wire Connectors, which is copyrighted by Underwriters Laboratories, Inc., Northbrook, Illinois. While use of this material has been authorized, UL shall not be responsible for the manner in which the information is presented, nor for any interpretations thereof.
Related Code Sections
E3406.9 General Requirements, Fine Stranded Conductors
Connectors and terminals for conductors that are more finely stranded than Class B and Class C stranding as shown in Table E3406.9, shall ...
2015 Virginia Residential Code > 34 General Requirements > E3406 Electrical Conductors and Connections > E3406.9 Fine Stranded Conductors
E3406.9 General Requirements, Fine Stranded Conductors
Connectors and terminals for conductors that are more finely stranded than Class B and Class C stranding as shown in Table E3406.9, shall ...
2012 Virginia Residential Code > 34 General Requirements > E3406 Electrical Conductors and Connections > E3406.9 Fine Stranded Conductors
E3908.8 Power and Lighting Distribution, Types of Equipment Grounding Conductors
copper, aluminum or copper-clad conductor.This conductor shall be solid or stranded; insulated, covered or bare; and in the form of a wire or a busbar ...
2012 Virginia Residential Code > 39 Power and Lighting Distribution > E3908 Grounding > E3908.8 Types of Equipment Grounding Conductors
E3908.8 Power and Lighting Distribution, Types of Equipment Grounding Conductors
copper, aluminum or copper-clad conductor.This conductor shall be solid or stranded; insulated, covered or bare; and in the form of a wire or a busbar ...
2015 Virginia Residential Code > 39 Power and Lighting Distribution > E3908 Grounding > E3908.8 Types of Equipment Grounding Conductors
Section 1104 Storm Drainage, Conductors and Connections
Conductor pipes shall not be used as soil, waste or vent pipes, and soil, waste or vent pipes shall not be used as conductors ...