E4207.3.1 Fifteen Volts or Less
JUMP TO FULL CODE CHAPTER
A luminaire installed in or on the wall of a storable pool shall be part of a cord and plug-connected lighting assembly. The assembly shall:
- Have a luminaire lamp that operates at 15 volts or less;
- Have an impact-resistant polymeric lens, luminaire body, and transformer enclosure;
- Have a transformer meeting the requirements of section E4206.1 with a primary rating not over 150 volts; and
- Have no exposed metal parts.
Related Code Sections
E4207.3.1 Swimming Pools, Fifteen Volts or Less
a luminaire lamp that operates at 15 volts or less; Have an impact-resistant polymeric lens, luminaire body, and transformer enclosure; Have ...
Residential Code 2009 > 42 Swimming Pools > E4207 Storable Swimming Pools > E4207.3 Luminaires > E4207.3.1 Fifteen Volts or Less
E4206.9.1 Swimming Pools, Junction Boxes
from the pool by a solid fence, wall or other permanent barrier. Where used on a lighting system operating at 15 volts or less, a flush deck box shall ...
Residential Code 2009 > 42 Swimming Pools > E4206 Equipment Installation > E4206.9 Junction Boxes and Enclosures for Transformers or Ground-Fault Circuit Interrupters > E4206.9.1 Junction Boxes
E4002.1 Devices and Luminaires, Rating and Type
Receptacles and cord connectors shall be rated at not less than 15 amperes, 125 volts, or 15 amperes, 250 volts, and shall not be a lampholder type ...
E4002.1 Devices and Luminaires, Rating and Type
Receptacles and cord connectors shall be rated at not less than 15 amperes, 125 volts, or 15 amperes, 250 volts, and shall not be a lampholder type ...
E4002.1 Devices and Luminaires, Rating and Type
Receptacles and cord connectors shall be rated at not less than 15 amperes, 125 volts, or 15 amperes, 250 volts, and shall not be a lampholder type ...