5703.6.9.1 Fiberglass-Reinforced Plastic Piping
JUMP TO FULL CODE CHAPTER
Fiberglass-reinforced plastic (FRP) piping is not required to be provided with flexible joints in locations where both of the following conditions are present:
- Piping does not exceed 4 inches (102 mm) in diameter.
- Piping has a straight run of not less than 4 feet (1219 mm) on one side of the connection where such connections result in a change of direction.
In lieu of the minimum 4-foot (1219 mm) straight run length, approved and listed flexible joints are allowed to be used under dispensers and suction pumps, at submerged pumps and tanks, and where vents extend above ground.
Related Code Sections
5703.6.9.1 Flammable and Combustible Liquids, Fiberglass-Reinforced Plastic Piping
Fiberglass-reinforced plastic (FRP) piping is not required to be provided with flexible joints in locations where both of the following conditions ...
California Fire Code 2019 > 57 Flammable and Combustible Liquids > 5703 General Requirements > 5703.6 Piping Systems > 5703.6.9 Flexible Joints > 5703.6.9.1 Fiberglass-Reinforced Plastic Piping
5703.6.9.1 Flammable and Combustible Liquids, Fiberglass-Reinforced Plastic Piping
Fiberglass-reinforced plastic (FRP) piping is not required to be provided with flexible joints in locations where both of the following conditions ...
California Fire Code 2016 > 57 Flammable and Combustible Liquids > 5703 General Requirements > 5703.6 Piping Systems > 5703.6.9 Flexible Joints > 5703.6.9.1 Fiberglass-Reinforced Plastic Piping
3203.7.1 High-Piled Combustible Storage, Group A Plastics
copolymer) Acetal (polyformaldehyde) Acrylic (polymethyl methacrylate) Butyl rubber EPDM (ethylene propylene rubber) FRP (fiberglass-reinforced ...
California Fire Code 2016 > 32 High-Piled Combustible Storage > 3203 Commodity Classification > 3203.7 Classification of Plastics > 3203.7.1 Group A Plastics