E4105.6 Feeders
JUMP TO FULL CODE CHAPTER
An equipment grounding conductor shall be installed with the feeder conductors between the grounding terminal of the pool equipment panelboard and the grounding terminal of the applicable service equipment or source of a separately derived system. The equipment grounding conductor shall be insulated, shall be sized in accordance with Table E3808.12, and shall be not smaller than 12 AWG
Exception: An existing feeder between an existing remote panelboard and service equipment shall be permitted to run in flexible metal conduit or an approved cable assembly that includes an equipment grounding conductor within its outer sheath. The equipment grounding conductor shall not be connected to the grounded conductor in the remote panelboard.
Exception: An existing feeder between an existing remote panelboard and service equipment shall be permitted to run in flexible metal conduit or an approved cable assembly that includes an equipment grounding conductor within its outer sheath. The equipment grounding conductor shall not be connected to the grounded conductor in the remote panelboard.
A feeder to a separate building or structure shall be permitted to supply swimming pool equipment branch circuits, or feeders supplying swimming pool equipment branch circuits, provided that the grounding arrangements in the separate building meet the requirements of Section E3507.3. Where installed in other than existing feeders covered in the exception to Section E4105.6, a separate equipment grounding conductor shall be an insulated conductor.
Related Code Sections
E4105.6 Swimming Pools, Feeders
An equipment grounding conductor shall be installed with the feeder conductors between the grounding terminal of the pool equipment panelboard ...
E4205.6 Swimming Pools, Feeders
An equipment grounding conductor shall be installed with the feeder conductors between the grounding terminal of the pool equipment panelboard ...
E4205.6 Swimming Pools, Feeders
These provisions shall apply to any feeder on the supply side of panelboards supplying branch circuits for pool equipment covered in this chapter ...
Section E3604 Branch Circuit and Feeder Requirements, Feeder Requirements
Feeder conductors that do not serve 100 percent of the dwelling unit load and branch-circuit conductors shall be of a size sufficient to carry ...
Section E3704 Branch Circuit and Feeder Requirements, Feeder Requirements
Feeder conductors that do not serve 100 percent of the dwelling unit load and branch-circuit conductors shall be of a size sufficient to carry ...
2020 Residential Code of New York State > 37 Branch Circuit and Feeder Requirements > E3704 Feeder Requirements