[F] 911.1 Features
JUMP TO FULL CODE CHAPTER
Where required by other sections of this code, a fire command center for fire department operations shall be provided. The location and accessibility of the fire command center shall be approved by the fire department. The fire command center shall be separated from the remainder of the building by not less than a 1-hour fire barrier constructed in accordance with Section 706 or horizontal assembly constructed in accordance with Section 711, or both. The room shall be a minimum of 96 square feet (9 m2) with a minimum dimension of 8 feet (2438 mm). A layout of the fire command center and all features required by the section to be contained therein shall be submitted for approval prior to installation. The fire command center shall comply with NFPA 72 and shall contain the following features:
- The emergency voice/alarm communication system unit.
- The fire department communications unit.
- Fire detection and alarm system annunciator unit.
- Annunciator unit visually indicating the location of the elevators and whether they are operational.
- Status indicators and controls for air-handling systems.
- The fire-fighter's control panel required by Section 909.16 for smoke control systems installed in the building.
- Controls for unlocking stairway doors simultaneously.
- Sprinkler valve and water-flow detector display panels.
- Emergency and standby power status indicators.
- A telephone for fire department use with controlled access to the public telephone system.
- Fire pump status indicators.
- Schematic building plans indicating the typical floor plan and detailing the building core, means of egress, fire protection systems, fire-fighting equipment and fire department access.
- Worktable.
- Generator supervision devices, manual start and transfer features.
- Public address system, where specifically required by other sections of this code.
Related Code Sections
509.1 Fire Service Features, Features
of the fire command center and all features required by this section to be contained therein shall be submitted for approval prior to installation. The fire ...
911.1 Fire Protection Systems, Features
features required by the section to be contained therein shall be submitted for approval prior to installation. The fire command center shall comply ...
2003.1 Manufacture of Organic Coatings, Building Features
Manufacturing of organic coatings shall be done only in buildings that do not have pits or basements ...
2010 Fire Code of NY > 20 Manufacture of Organic Coatings > 2003 General Precautions > 2003.1 Building Features
2903.1 Manufacture of Organic Coatings, Building Features
Manufacturing of organic coatings shall be done only in buildings that do not have pits or basements ...
Fire Code 2015 of New York State > 29 Manufacture of Organic Coatings > 2903 General Precautions > 2903.1 Building Features
2903.1 Manufacture of Organic Coatings, Building Features
Manufacturing of organic coatings shall be done only in buildings that do not have pits or basements ...
2020 Fire Code of NYS > 29 Manufacture of Organic Coatings > 2903 General Precautions > 2903.1 Building Features