(B) Fastened-in-Place Equipment
Go To Full Code Chapter
Equipment that is fastened in place shall be connected to the premises wiring system by one of the following methods:
- A nonlocking, 2-pole, 3-wire grounding-type receptacle outlet rated 125 volts or 250 volts, single phase, up to 50 amperes
- A nonlocking, 3-pole, 4-wire grounding-type receptacle outlet rated 250 volts, three phase, up to 50 amperes
- A nonlocking, 3-pole, 4-wire grounding-type receptacle outlet rated 250 volts, single phase, 30 or 50 amperes
- A nonlocking, 2-pole, 3-wire grounding-type receptacle outlet rated 60 volts dc maximum, 15 or 20 amperes
Related Code Sections
(B) Special Equipment, Fastened-in-Place Equipment
Equipment that is fastened in place shall be connected to the premises wiring system by one of the following methods: A nonlocking, 2-pole, 3-wire ...
(2) Wiring and Protection, Utilization Equipment Fastened in Place
The total rating of utilization equipment fastened in place, other than luminaires, shall not exceed 50 percent of the branch-circuit ampere rating ...
(2) Wiring and Protection, Utilization Equipment Fastened in Place
The total rating of utilization equipment fastened in place, other than luminaires, shall not exceed 50 percent of the branch-circuit ampere rating ...
220.53 Wiring and Protection, Appliance Load — Dwelling Unit(s)
This demand factor shall not apply to:
Household electric cooking equipment that is fastened in place
Clothes dryers
Space heating equipment ...
(2) Special Equipment, Fastened in Place
Where the electric vehicle supply equipment or charging system is fastened in place, the usable length of the output cable shall be measured from ...