// CODE SNIPPET
6.5.3.2.1 Supply Fan Airflow Control
Go To Full Code Chapter
Each cooling system listed in Table 6.5.3.2.1 shall be designed to vary the supply fan airflow as a function of load and shall comply with the following requirements:
- DX and chilled-water cooling units that control the capacity of the mechanical cooling directly based on space temperature shall have a minimum of two stages of fan control. Low or minimum speed shall not exceed 66% of full speed. At low or minimum speed, the fan system shall draw no more than 40% of the fan power at full fan speed. Low or minimum speed shall be used during periods of low cooling load and ventilation-only operation.
- All other units, including DX cooling units and chilled-water units that control the space temperature by modulating the airflow to the space, shall have modulating fan control. Minimum speed shall not exceed 50% of full speed. At minimum speed, the fan system shall draw no more than 30% of the power at full fan speed. Low or minimum speed shall be used during periods of low cooling load and ventilation-only operation.
- Units that include an air-side economizer to meet the requirements of Section 6.5.1 shall have a minimum of two speeds of fan control during economizer operation.
Exceptions:
- Modulating fan control is not required for chilled-water and evaporative cooling units with <1 hp fan motors if the units are not used to provide ventilation air and the indoor fan cycles with the load.
- If the volume of outdoor air required to meet the ventilation requirements of Standard 62.1 at low speed exceeds the air that would be delivered at the speed defined in Section 6.5.3.2.1(a) or 6.5.3.2.1(b) then the minimum speed shall be selected to provide the required ventilation air.
TABLE 6.5.3.2.1 Effective Dates for Fan Control
Cooling System Type | Fan Motor Size, hp | Mechanical Cooling Capacity, Btu/h | Effective Date |
---|---|---|---|
DX cooling | Any | ≥110,000 | |
≥75,000 | 1/1/2014 | ||
≥65,000 | 1/1/2016 | ||
Chilled-water and evaporative cooling | ≥5 | Any | |
≥1/4 | Any | 1/1/2014 |
Upcodes Diagrams
Related Code Sections
6.5.3.2.1 Heating, Ventilating, and Air Conditioning, Supply Fan Airflow Control
Each cooling system listed in Table 6.5.3.2.1 shall be designed to vary the supply fan airflow as a function of load and shall comply ...
6.5.3.2.1 Heating, Ventilating, and Air Conditioning, Supply Fan Airflow Control
Each cooling system listed in Table 6.5.3.2.1 shall be designed to vary the supply fan airflow as a function of load and shall comply ...
6.5.3.2.1 Heating, Ventilating, and Air Conditioning, Supply Fan Airflow Control
Each cooling system listed in Table 6.5.3.2.1 shall be designed to vary the supply fan airflow as a function of load and shall comply ...
6.1.1.3.1 Heating, Ventilating, and Air Conditioning,
Efficiency" 6.5.3.2.1, "Supply Fan Airflow Control" 6.5.3.6, "Fractional Horsepower Fan Motors" 6.5.4.1, "Boiler Turndown" 6.5.4.3, "Chiller ...
6.1.1.3.1 Heating, Ventilating, and Air Conditioning,
Efficiency" 6.5.3.2.1, "Supply Fan Airflow Control" 6.5.3.6, "Fractional Horsepower Kilowatt Fan Motors" 6.5.4.1, "Boiler Turndown" 6.5.4.3 ...