1607.10.4 Fall Arrest and Lifeline Anchorages
JUMP TO FULL CODE CHAPTER
In addition to any other applicable live loads, fall arrest and lifeline anchorages and structural elements that support these anchorages shall be designed for a live load of not less than 3,100 pounds (13.8 kN) for each attached lifeline, in every direction that a fall arrest load can be applied.