R1005.7 Factory-Built Chimney Offsets
JUMP TO FULL CODE CHAPTER
Where a factory-built chimney assembly incorporates offsets, no part of the chimney shall be at an angle of more than 30 degrees (0.52 rad) from vertical at any point in the assembly and the chimney assembly shall not include more than four elbows.
Related Code Sections
805.3 Chimneys and Vents, Factory-Built Chimney Offsets
Where a factory-built chimney assembly incorporates offsets, no part of the chimney shall be at an angle of more than 30 degrees (0.52 rad) from ...
Mechanical Code 2015 of Utah > 8 Chimneys and Vents > 805 Factory-Built Chimneys > 805.3 Factory-Built Chimney Offsets
805.4 Chimneys and Vents, Factory-Built Chimney Offsets
Where a factory-built chimney assembly incorporates offsets, no part of the chimney shall be at an angle of more than 30 degrees (0.52 rad) from ...
Mechanical Code 2018 of Utah > 8 Chimneys and Vents > 805 Factory-Built Chimneys > 805.4 Factory-Built Chimney Offsets
R1005.7 Chimneys and Fireplaces, Factory-Built Chimney Offsets
Where a factory-built chimney assembly incorporates offsets, no part of the chimney shall be at an angle of more than 30 degrees (0.52 rad) from ...
Residential Code 2015 of Utah > 10 Chimneys and Fireplaces > R1005 Factory-Built Chimneys > R1005.7 Factory-Built Chimney Offsets
503.5.1 Chimneys and Vents, Factory-Built Chimneys
Factory-built chimneys shall be installed in accordance with the manufacturer's instructions. Factory-built chimneys used to vent appliances ...
Fuel Gas Code 2015 of Utah > 5 Chimneys and Vents > 503 (IFGS) Venting of Appliances > 503.5 Masonry, Metal and Factory-Built Chimneys > 503.5.1 Factory-Built Chimneys
503.5.1 Chimneys and Vents, Factory-Built Chimneys
Factory-built chimneys shall be listed in accordance with UL 103 and installed in accordance with the manufacturer's instructions. Factory-built ...
Fuel Gas Code 2018 of Utah > 5 Chimneys and Vents > 503 (IFGS) Venting of Appliances > 503.5 Masonry, Metal and Factory-Built Chimneys > 503.5.1 Factory-Built Chimneys