[F] 906.9.1 Extinguishers Weighing 40 Pounds or Less
JUMP TO FULL CODE CHAPTER
Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that their tops are not more than 5 feet (1524 mm) above the floor.
Related Code Sections
906.9.1 Fire Protection Systems, Extinguishers Weighing 40 Pounds or Less
Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that their tops are not more than 5 feet ...
Building Code 2015 of Utah > 9 Fire Protection Systems > 906 Portable Fire Extinguishers > 906.9 Extinguisher Installation > 906.9.1 Extinguishers Weighing 40 Pounds or Less
906.9.1 Fire Protection and Life Safety Systems, Extinguishers Weighing 40 Pounds or Less
Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that their tops are not more than 5 feet ...
Building Code 2018 of Utah > 9 Fire Protection and Life Safety Systems > 906 Portable Fire Extinguishers > 906.9 Extinguisher Installation > 906.9.1 Extinguishers Weighing 40 Pounds or Less
906.9.1 Fire Protection and Life Safety Systems, Extinguishers Weighing 40 Pounds or Less
Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that their tops are not more than 5 feet ...
Fire Code 2018 of Utah > 9 Fire Protection and Life Safety Systems > 906 Portable Fire Extinguishers > 906.9 Extinguisher Installation > 906.9.1 Extinguishers Weighing 40 Pounds or Less
906.9 Fire Protection Systems, Extinguisher Installation
Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall ...
Building Code 2015 of Utah > 9 Fire Protection Systems > 906 Portable Fire Extinguishers > 906.9 Extinguisher Installation
5705.4.9 Flammable and Combustible Liquids, Portable Fire Extinguishers
Approved portable fire extinguishers shall be provided in accordance with Section 906. Not less than one portable fire extinguisher having a rating ...
Fire Code 2018 of Utah > 57 Flammable and Combustible Liquids > 5705 Dispensing, Use, Mixing and Handling > 5705.4 Solvent Distillation Units > 5705.4.9 Portable Fire Extinguishers