Externally illuminated exit signs shall comply with Sections 1013.6.1 through 1013.6.3.
1013.6.1 Graphics
Every exit sign and directional exit sign shall have plainly legible letters not less than 6 inches (152 mm) high with the principal strokes of the letters not less than 3/4 inch (19.1 mm) wide. The word "EXIT" shall have letters having a width not less than 2 inches (51 mm) wide, except the letter "I," and the minimum spacing between letters shall be not less than 3/8 inch (9.5 mm). Signs larger than the minimum established in this section shall have letter widths, strokes and spacing in proportion to their height.
The word "EXIT" shall be in high contrast with the background and shall be clearly discernible when the means of exit sign illumination is or is not energized. If a chevron directional indicator is provided as part of the exit sign, the construction shall be such that the direction of the chevron directional indicator cannot be readily changed.
1013.6.2 Exit Sign Illumination
The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 footcandles (54 lux).
1013.6.3 Power Source
Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Chapter 27. Group I-2, Condition 2 exit sign illumination shall not be provided by unit equipment batteries only.
Exception: Approved exit sign illumination types that provide continuous illumination independent of external power sources for a duration of not less than 90 minutes, in case of primary power loss, are not required to be connected to an emergency electrical system.

Related Code Sections

1013.6.1 Means of Egress, Graphics
be clearly discernible when the means of exit sign illumination is or is not energized. If a chevron directional indicator is provided as part of the exit ...
Section 1013 Means of Egress, Exit Signs
The face of an exit sign illuminated from an external source shall ...
Section 1013 Means of Egress, Exit Signs
Externally illuminated exit signs shall comply with Sections 1013.6.1 ...