3206.7.1 Exterior Walls Without Fire Department Access Doors
JUMP TO FULL CODE CHAPTER
Fire department access doors are not required in an exterior wall that does not face a fire apparatus access road provided that all of the following conditions occur:
- The opposite exterior wall faces a fire apparatus access road.
- The opposite exterior wall is provided with fire department access doors.
- The entire interior surface of the exterior wall is less than 150 feet (45 720 mm) away from a fire department access door.
- The building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
Related Code Sections
3206.7.1 High-Piled Combustible Storage, Exterior Walls Without Fire Department Access Doors
Fire department access doors are not required in an exterior wall that does not face a fire apparatus access road provided that all of the following ...
Fire Code 2018 of Kansas > 32 High-Piled Combustible Storage > 3206 General Fire Protection and Life Safety Features > 3206.7 Fire Department Access Doors > 3206.7.1 Exterior Walls Without Fire Department Access Doors
504.2 Fire Service Features, Maintenance of Exterior Doors and Openings
background. Required fire department access doors shall not be obstructed or eliminated. Exit and exit access doors shall comply with Chapter 10. Access ...
Fire Code 2018 of Kansas > 5 Fire Service Features > 504 Access to Building Openings and Roofs > 504.2 Maintenance of Exterior Doors and Openings
504.1 Fire Service Features, Required Access
by the fire department. An approved access walkway leading from fire apparatus access roads to exterior openings shall be provided where required ...
Fire Code 2018 of Kansas > 5 Fire Service Features > 504 Access to Building Openings and Roofs > 504.1 Required Access
912.4 Fire Protection and Life Safety Systems, Access
Immediate access to fire department connections shall be maintained at all times and without obstruction by fences, bushes, trees, walls or any other ...
Fire Code 2018 of Kansas > 9 Fire Protection and Life Safety Systems > 912 Fire Department Connections > 912.4 Access
912.4 Fire Protection and Life Safety Systems, Access
Immediate access to fire department connections shall be maintained at all times and without obstruction by fences, bushes, trees, walls or any other ...
Building Code 2018 of Kansas > 9 Fire Protection and Life Safety Systems > 912 Fire Department Connections > 912.4 Access