1026.6 Exterior Stairway and Ramp Protection
JUMP TO FULL CODE CHAPTER
Exterior exit stairways and ramps shall be separated from the interior of the building as required in Section 1022.2. Openings shall be limited to those necessary for egress from normally occupied spaces.
Exceptions:
- Separation from the interior of the building is not required for occupancies, other than those in Group R-1 or R-2, in buildings that are no more than two stories above grade plane where a level of exit discharge serving such occupancies is the first story above grade plane.
- Separation from the interior of the building is not required where the exterior stairway or ramp is served by an exterior ramp or balcony that connects two remote exterior stairways or other approved exits with a perimeter that is not less than 50 percent open. To be considered open, the opening shall be a minimum of 50 percent of the height of the enclosing wall, with the top of the openings no less than 7 feet (2134 mm) above the top of the balcony.
- Separation from the interior of the building is not required for an exterior stairway or ramp located in a building or structure that is permitted to have unenclosed exit access stairways in accordance with Section 1009.3.
- Separation from the interior of the building is not required for exterior stairways or ramps connected to open-ended corridors, provided that Items 4.1 through 4.5 are met:
- The building, including corridors, stairways or ramps, shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
- The open-ended corridors comply with Section 1018.
- The open-ended corridors are connected on each end to an exterior exit stairway or ramp complying with Section 1026.
- The exterior walls and openings adjacent to the exterior exit stairway or ramp comply with Section 1022.7.
- At any location in an open-ended corridor where a change of direction exceeding 45 degrees (0.79 rad) occurs, a clear opening of not less than 35 square feet (3.3 m2) or an exterior stairway or ramp shall be provided. Where clear openings are provided, they shall be located so as to minimize the accumulation of smoke or toxic gases.
Related Code Sections
1026.6 Means of Egress, Exterior Stairway and Ramp Protection
Exterior exit stairways and ramps shall be separated from the interior of the building as required in Section 1022.2. Openings shall be limited ...
Georgia State Minimum Standard Building Code > 10 Means of Egress > 1026 Exterior Exit Stairways and Ramps > 1026.6 Exterior Stairway and Ramp Protection
1026.6 Means of Egress, Exterior Stairway and Ramp Protection
Exterior exit stairways and ramps shall be separated from the interior of the building as required in Section 1022.7. Openings shall be limited ...
Georgia State Minimum Standard Fire Code > 10 Means of Egress > 1026 Exterior Exit Stairways and Ramps > 1026.6 Exterior Stairway and Ramp Protection
1027.6 Means of Egress, Exterior Exit Stairway and Ramp Protection
Exterior exit stairways and ramps shall be separated from the interior of the building as required in Section 1023.2. Openings shall be limited ...
Georgia State Minimum Fire Prevention Code > 10 Means of Egress > 1027 Exterior Exit Stairways and Ramps > 1027.6 Exterior Exit Stairway and Ramp Protection
1027.6 Means of Egress, Exterior Exit Stairway and Ramp Protection
Exterior exit stairways and ramps shall be separated from the interior of the building as required in Section 1023.2. Openings shall be limited ...
Georgia State Minimum Standard Building Code > 10 Means of Egress > 1027 Exterior Exit Stairways and Ramps > 1027.6 Exterior Exit Stairway and Ramp Protection
1022.4 Means of Egress, Openings
Interior exit stairway and ramp opening protectives shall be in accordance with the requirements of Section 716. Openings in interior exit ...
Georgia State Minimum Standard Building Code > 10 Means of Egress > 1022 Interior Exit Stairways and Ramps > 1022.4 Openings