409.1.1 Exterior Lighting Zones
JUMP TO FULL CODE CHAPTER
The lighting zone for the building site shall be determined from Table 409.1.1 unless otherwise specified by the jurisdiction.
[E] TABLE 409.1.1
EXTERIOR LIGHTING ZONES
EXTERIOR LIGHTING ZONES
LIGHTING ZONE | DESCRIPTION |
1 | Developed areas of national parks, state parks, forest land and rural areas |
2 | Areas predominantly consisting of residential zoning, neighborhood business districts, light industrial with limited nighttime use and residential mixed use areas |
3 | All other areas |
4 | High-activity commercial districts in major metropolitan areas as designated by the local jurisdiction |
Related Code Sections
409.1.1 Site Development and Land Use, Exterior Lighting Zones
EXTERIOR LIGHTING ZONES LIGHTING ZONE DESCRIPTION 1 Developed areas of national parks, state parks, forest land and rural areas 2 ...
Green Construction Code 2012 of Maryland > 4 Site Development and Land Use > 409 Site Lighting > 409.1 Light Pollution Control > 409.1.1 Exterior Lighting Zones
C405.4.2 [CE] Commercial Energy Efficiency, Exterior Lighting Power Allowance
lighting zone for the building exterior is determined in accordance with Table C405.4.2(1) unless otherwise specified by the code official . TABLE ...
Energy Conservation Code 2018 of Maryland > 4 [CE] Commercial Energy Efficiency > C405 Electrical Power and Lighting Systems > C405.4 Exterior Lighting Power Requirements (Mandatory) > C405.4.2 Exterior Lighting Power Allowance
C405.5 [CE] Commercial Energy Efficiency, Exterior Lighting (Mandatory)
lighting zone. Trade-offs are allowed only among exterior lighting applications listed in Table C405.5.1(2), in the Tradable Surfaces section. The ...
Energy Conservation Code 2015 of Maryland > 4 [CE] Commercial Energy Efficiency > C405 Electrical Power and Lighting Systems > C405.5 Exterior Lighting (Mandatory)
Section C405 [CE] Commercial Energy Efficiency, Electrical Power and Lighting Systems
Trade-offs are allowed only among exterior lighting applications listed in Table C405.5.1(2), in the Tradable Surfaces section. The lighting zone ...
Energy Conservation Code 2015 of Maryland > 4 [CE] Commercial Energy Efficiency > C405 Electrical Power and Lighting Systems
Section C405 [CE] Commercial Energy Efficiency, Electrical Power and Lighting Systems
lighting zone for the building exterior is determined in accordance with Table C405.4.2(1) unless otherwise specified by the code official . TABLE ...
Energy Conservation Code 2018 of Maryland > 4 [CE] Commercial Energy Efficiency > C405 Electrical Power and Lighting Systems