1007.7 Exterior Area for Assisted Rescue
JUMP TO FULL CODE CHAPTER
The exterior area for assisted rescue must be open to the outside air and meet the requirements of Section 1007.6.1. Separation walls shall comply with the requirements of Section 705 for exterior walls. Where walls or openings are between the area for assisted rescue and the interior of the building, the building exterior walls within 10 feet (3048 mm) horizontally of a nonrated wall or unprotected opening shall have a fire-resistance rating of not less than 1 hour. Openings within such exterior walls shall be protected by opening protectives having a fire protection rating of not less than 3/4 hour. This construction shall extend vertically from the ground to a point 10 feet (3048 mm) above the floor level of the area for assisted rescue or to the roof line, whichever is lower.
Exterior exit stairways that are part of the accessible means of egress for the exterior area for assisted rescue shall provide a clear width of 48 inches (1219 mm) between handrails.
Related Code Sections
1007.7 Means of Egress, Exterior Area for Assisted Rescue
The exterior area for assisted rescue must be open to the outside air and meet the requirements of Section 1007.6.1. Separation walls shall comply ...
NYC Building Code 2014 > 10 Means of Egress > 1007 Accessible Means of Egress > 1007.7 Exterior Area for Assisted Rescue
1007.8 Means of Egress, Exterior Area for Assisted Rescue
The exterior area for assisted rescue must be open to the outside air and meet the requirements of Section 1007.6.1. Separation walls shall comply ...
NYC Building Code 2008 > 10 Means of Egress > 1007 Accessible Means of Egress > 1007.8 Exterior Area for Assisted Rescue
1007.9 Means of Egress, Signage
an adjacent floor area shall be identified by a sign stating: AREA OF RESCUE ASSISTANCE. Each door providing access to an exterior area for assisted ...
1007.2.2 Means of Egress, Exit Discharge
Where an exit discharge is not accessible, an exterior area for assisted rescue shall be provided in accordance with Section 1007.8. An exterior area ...
NYC Building Code 2008 > 10 Means of Egress > 1007 Accessible Means of Egress > 1007.2 Continuity and Components > 1007.2.2 Exit Discharge
1007.2.2 Means of Egress, Exit Discharge
Where an exit discharge is not accessible, an exterior area for assisted rescue shall be provided in accordance with Section 1007.7. An exterior area ...
NYC Building Code 2014 > 10 Means of Egress > 1007 Accessible Means of Egress > 1007.2 Continuity and Components > 1007.2.2 Exit Discharge