24.5.3 Extended Coverage Spacing Sprinklers
Go To Full Code Chapter
24.5.3.1
Sprinklers having extended coverage areas requiring up to 10 sprinklers to be included in the hydraulic calculation shall be installed in accordance with the obstruction criteria described in 11.2.5.1, 14.2.11.2, and 14.2.11.3, unless large-scale fire testing is conducted with a representative obstruction below the sprinkler that demonstrates equivalent performance.
24.5.3.2
CMDA and CMSA sprinklers having extended coverage areas requiring more than 10 sprinklers in the design area shall be installed in accordance with the obstructions to sprinkler discharge criteria described in 13.2.8 and 11.2.5.1.
24.5.3.2.1
ESFR sprinklers having extended coverage areas requiring more than 10 sprinklers in the design area shall be installed in accordance with the obstructions to sprinkler discharge criteria described in 14.2.11.2 and 14.2.11.3.
24.5.3.2.2
Other obstruction criteria shall be acceptable if large-scale fire testing is conducted with a representative obstruction below the sprinkler that demonstrates equivalent performance.
24.5.3.2.3
When utilizing upright CMSA, CMDA, or ESFR sprinklers, any continuous obstruction 4 in. (100 mm) or less shall be permitted to be ignored.
Related Code Sections
21.5.3 Alternative Sprinkler System Designs for Chapters 12 Through 20, Extended Coverage Spacing Sprinklers
Sprinklers having extended coverage areas requiring up to 10 sprinklers to be included in the hydraulic calculation shall be installed in accordance ...
21.5.3 Alternative Sprinkler System Designs for Chapters 12 Through 20, Extended Coverage Spacing Sprinklers
Sprinklers having extended coverage areas requiring up to 10 sprinklers to be included in the hydraulic calculation shall be installed in accordance ...
24.5.3 Alternative Sprinkler System Designs for Chapters 20 Through 25, Extended Coverage Spacing Sprinklers
Sprinklers having extended coverage areas requiring up to 10 sprinklers to be included in the hydraulic calculation shall be installed in accordance ...
24.5.3.2.1 Alternative Sprinkler System Designs for Chapters 20 Through 25,
ESFR sprinklers having extended coverage areas requiring more than 10 sprinklers in the design area shall be installed in accordance ...
21.5.3.1 Alternative Sprinkler System Designs for Chapters 12 Through 20,
Sprinklers having extended coverage areas requiring up to 10 sprinklers to be included in the hydraulic calculation shall be installed in accordance ...