720.3 Exposed Installation
JUMP TO FULL CODE CHAPTER
Insulating materials, where exposed as installed in buildings of any type of construction, shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 450.
Exception: Cellulosic fiber loose-fill insulation complying with the requirements of Section 720.6 shall not be required to meet a flame spread index requirement but shall be required to meet a smoke-developed index of not more than 450 when tested in accordance with CAN/ULC S102.2.
Exposed insulation materials installed on attic floors shall have a critical radiant flux of not less than 0.12 watt per square centimeter when tested in accordance with ASTM E970.
Related Code Sections
720.3 Fire and Smoke Protection Features, Exposed Installation
Insulating materials, where exposed as installed in buildings of any type of construction, shall have a flame spread index of not more than 25 ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 720 Thermal- And Sound-Insulating Materials > 720.3 Exposed Installation
720.3 Fire and Smoke Protection Features, Exposed Installation
Insulating materials, where exposed as installed in buildings of any type of construction, shall have a flame spread index of not more than 25 ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 720 Thermal- And Sound-Insulating Materials > 720.3 Exposed Installation
300.39 Wiring Methods and Materials, Braid-Covered Insulated Conductors — Exposed Installation
Exposed runs of braid-covered insulated conductors shall have a flame-retardant braid. If the conductors used do not have this protection, a flame ...
National Electrical Code 2017 of Illinois > 3 Wiring Methods and Materials > 300 General Requirements for Wiring Methods and Materials > 300.39 Braid-Covered Insulated Conductors — Exposed Installation
300.39 Wiring Methods and Materials, Braid-Covered Insulated Conductors — Exposed Installation
Exposed runs of braid-covered insulated conductors shall have a flame-retardant braid. If the conductors used do not have this protection, a flame ...
National Electrical Code 2020 of Illinois > 3 Wiring Methods and Materials > 300 General Requirements for Wiring Methods and Materials > 300.39 Braid-Covered Insulated Conductors — Exposed Installation
16.2.2.1.2 Installation of Piping, Valves, and Appurtenances,
of the sprinkler in the approved manner so that no part of the sprinkler will be exposed after installation has been completed ...
Standard for the Installation of Sprinkler Systems 2019 of Illinois > 16 Installation of Piping, Valves, and Appurtenances > 16.2 Sprinkler Installation > 16.2.2 Corrosion Resistant > 16.2.2.1 > 16.2.2.1.2