R403.1.8.1 Expansive Soils Classifications
JUMP TO FULL CODE CHAPTER
Soils meeting all four of the following provisions shall be considered expansive, except that tests to show compliance with Items 1, 2 and 3 shall not be required if the test prescribed in Item 4 is conducted:
- Plasticity Index (PI) of 15 or greater, determined in accordance with ASTM D4318.
- More than 10 percent of the soil particles pass a No. 200 sieve (75 μm), determined in accordance with ASTM D422.
- More than 10 percent of the soil particles are less than 5 micrometers in size, determined in accordance with ASTM D422.
- Expansion Index greater than 20, determined in accordance with ASTM D4829.
Related Code Sections
R403.1.8.1 Foundations, Expansive Soils Classifications
Soils meeting all four of the following provisions shall be considered expansive, except that tests to show compliance with Items 1, 2 and 3 shall ...
2015 Michigan Residential Code > 4 Foundations > R403 Footings > R403.1 General > R403.1.8 Foundations on Expansive Soils > R403.1.8.1 Expansive Soils Classifications
AE502.2 Manufactured Housing Used as Dwellings, Soil Classification
, compressibility and expansiveness.
When required by the building official, the soil classification
design-bearing capacity ...
2015 Michigan Residential Code > E Manufactured Housing Used as Dwellings > AE502 Foundation Systems > AE502.2 Soil Classification
R405.1 Foundations, Concrete or Masonry Foundations
to the Unified Soil Classification
System, Group I soils, as detailed in Table R405.1.
TABLE R405.1 PROPERTIES OF SOILS CLASSIFIED ...
2015 Michigan Residential Code > 4 Foundations > R405 Foundation Drainage > R405.1 Concrete or Masonry Foundations
1803.3 Soils and Foundations, Basis of Investigation
Soil classification shall be
based on observation and any necessary tests of the materials disclosed by borings, test pits or other subsurface ...
2015 Michigan Building Code > 18 Soils and Foundations > 1803 Geotechnical Investigations > 1803.3 Basis of Investigation
1808.6 Soils and Foundations, Design for Expansive Soils
Foundations for buildings
and structures founded on expansive soils shall be designed
in accordance with Section 1808.6.1 or 1808.6.2 ...
2015 Michigan Building Code > 18 Soils and Foundations > 1808 Foundations > 1808.6 Design for Expansive Soils