Section 1022 Exits

Go To Full Code Chapter
1022.1 General
Exits shall comply with Sections 1022 through 1027 and the applicable requirements of Sections 1003 through 1015. An exit shall not be used for any purpose that interferes with its function as a means of egress. Once a given level of exit protection is achieved, such level of protection shall not be reduced until arrival at the exit discharge. Exits shall be continuous from the point of entry into the exit to the exit discharge.
1022.2 Exterior Exit Doors
Buildings or structures used for human occupancy shall have not less than one exterior door that meets the requirements of Section 1010.1.1.
1022.2.1 Detailed Requirements
Exterior exit doors shall comply with the applicable requirements of Section 1010.1.
1022.2.2 Arrangement
Exterior exit doors shall lead directly to the exit discharge or the public way.