509.3.3.5 Exit Terminals
JUMP TO FULL CODE CHAPTER
The exit terminals of
mechanical draft systems shall be not less than 7 feet
(2134 mm) above finished ground level where
located adjacent to public walkways and shall be
located as specified in Section 509.8 and Section
509.8.1 of this code. [NFPA 54:12.4.3.6]
Related Code Sections
509.3.3.5 Water Heaters, Exit Terminals
The exit terminals of mechanical draft systems shall be not less than 7 feet (2134 mm) above finished ground level where located adjacent to public ...
California Plumbing Code 2016 > 5 Water Heaters > 509.0 Venting of Appliances > 509.3 Design and Construction > 509.3.3 Mechanical Draft Systems > 509.3.3.5 Exit Terminals
509.3.3.5 Water Heaters, Exit Terminals
The exit terminals of
mechanical draft systems shall be not less than 7 feet
(2134 mm) above finished ground level where
located adjacent to public ...
California Plumbing Code 2019 > 5 Water Heaters > 509.0 Venting of Appliances > 509.3 Design and Construction > 509.3.3 Mechanical Draft Systems > 509.3.3.5 Exit Terminals
802.3.3.5 Chimneys and Vents, Exit Terminals
The exit terminals of
mechanical draft systems shall be not less than 7 feet
(2134 mm) above finished ground level where
located adjacent to public ...
California Mechanical Code 2016 > 8 Chimneys and Vents > 802.0 Venting of Appliances > 802.3 Design and Construction > 802.3.3 Mechanical Draft Systems > 802.3.3.5 Exit Terminals
802.3.3.5 Chimneys and Vents, Exit Terminals
The exit terminals of
mechanical draft systems shall be not less than 7 feet
(2134 mm) above finished ground level where
located adjacent to public ...
California Mechanical Code 2019 > 8 Chimneys and Vents > 802.0 Venting of Appliances > 802.3 Design and Construction > 802.3.3 Mechanical Draft Systems > 802.3.3.5 Exit Terminals
1024.4 Means of Egress, Termination
Exit passageways on the level of exit discharge shall terminate at an exit discharge. Exit passageways on other levels shall terminate at an exit ...