Two exits or exit access doorways from any space shall be provided where one of the following conditions exists:
  1. The occupant load of the space exceeds the values in Table 1014.1.
  2. The common path of egress travel exceeds the limitations of Section 1013.3.
  3. Where required by Sections 1014.3, 1014.4 and 1014.5.
  Exception: Group I-2 occupancies shall comply with Section 1013.2.2.

TABLE 1014.1
SPACES WITH ONE MEANS OF EGRESS
OCCUPANCY MAXIMUM OCCUPANT LOAD
A, B, E, M, U 74
F 50
H-1, H-2, H-3 3
H-4, H-5, I-1, I-3, I-4 10
I-2 See Section 1013.2.2
R 20
S 30
1014.1.1 Three or More Exits
Access to three or more exits shall be provided from a floor area where required by Section 1018.1.

Related Code Sections

1014.1 Means of Egress, Exit or Exit Access Doorways Required
Two exits or exit access doorways from any space shall be provided where one of the following conditions exists:   1. The occupant load ...
1006.1 Means of Egress, General
The number of exits or exit access doorways required within the means of egress system shall comply with the provisions of Section 1006.2 for spaces ...
1007.1.2 Means of Egress, Three or More Exits or Exit Access Doorways
Where access to three or more exits is required, not less than two exit or exit access doorways shall be arranged in accordance with the provisions ...
1015.2 Means of Egress, Exit or Exit Access Doorway Arrangement
Where two exits or exit access doorways are required from any portion of the exit access, the exit doors or exit access ...
Section 1007 Means of Egress, Exit and Exit Access Doorway Configuration
exits, exit access doorways, exit access stairways or ramps, or any combination thereof, are required from any portion of the exit access, they shall ...