1015.2 Exit or Exit Access Doorway Arrangement
Go To Full Code Chapter
1015.2.1 Two Exits or Exit Access Doorways
Where two exits or exit access doorways are required from any portion of the exit access, the exit doors or exit access doorways shall be placed a distance apart equal to not less than one-half of the length of the maximum overall diagonal dimension of the building or area to be served measured in a straight line between exit doors or exit access doorways. Interlocking or scissor stairs shall be counted as one exit stairway.
Exceptions:
- Where interior exit stairways are interconnected by a 1-hour fire-resistance-rated corridor conforming to the requirements of Section 1018, the required exit separation shall be measured along the shortest direct line of travel within the corridor.
- Where a building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2, the separation distance of the exit doors or exit access doorways shall not be less than one-third of the length of the maximum overall diagonal dimension of the area served.
1015.2.2 Three or More Exits or Exit Access Doorways
Where access to three or more exits is required, at least two exit doors or exit access doorways shall be arranged in accordance with the provisions of Section 1015.2.1.
Related Code Sections
1015.2 Means of Egress, Exit or Exit Access Doorway Arrangement
or exit access doorways shall be arranged in accordance with the provisions of Section 1015.2.1 ...
1015.2 Means of Egress, Exit or Exit Access Doorway Arrangement
exit doors or exit access doorways shall be arranged in accordance with the provisions of Section 1015.2.1 ...
1007.1.2 Means of Egress, Three or More Exits or Exit Access Doorways
Where access to three or more exits is required, not less than two exit or exit access doorways shall be arranged in accordance with the provisions ...
1007.1.2 Means of Egress, Three or More Exits or Exit Access Doorways
Where access to three or more exits is required, not less than two exit or exit access doorways shall be arranged in accordance with the provisions ...
Section 1007 Means of Egress, Exit and Exit Access Doorway Configuration
access doorways shall be arranged in accordance with the provisions of Section 1007.1.1. Additional required exit or exit access doorways shall ...