// CODE SNIPPET
1113.6.1 Exit Ladder Devices
Go To Full Code Chapter
1113.6.1.1 Scope
This standard for exit ladder devices is applicable where such devices are permitted by the building official for installation on existing apartment houses and hotels in conformance with the California Building Code.
1113.6.1.2 Instructions
Installation shall be in accordance with the manufacturer's instructions. Instructions shall be illustrated and shall include directions and information adequate for attaining proper and safe installation of the product. Where exit ladder devices are intended for mounting on different support surfaces, specific installation instructions shall be provided for each surface.
1113.6.1.3 General Design
All load-bearing surfaces and supporting hardware shall be of noncombustible materials. Exit ladder devices shall have a minimum width of 12 inches (305 mm) when in the position intended for use. The design load shall not be less than 400 pounds (1780 N) for 16-foot (4877 mm) length and 600 pounds (2699 N) for 25-foot (7620 mm) length.
1113.6.1.4 Performance
1113.6.1.4.1
1113.6.1.4.2
Exit ladder devices of the retractable type shall, in addition to the static load requirements of Section 413.6.1.4.1 of the California Building Code, be capable of withstanding the following tests:
- Rung strength
- Rung-to-side-rail shear strength
- Release mechanism
- Low temperature
1113.6.1.5 Rung-Strength Test
Rungs of retractable exit ladder devices shall be capable of withstanding a load of 1,000 pounds (4448 N) when applied to a 31/2-inch-wide (89 mm) block resting at the center of the rung. The test load shall be applied for a period of one hour. The ladder shall remain operational following this test.
1113.6.1.6 Rung-to-Side-Rail Shear Test
Rungs of retractable exit ladder devices shall be capable of withstanding 1,000 (4448 N) when applied to a 31/2-inch-wide (89 mm) block resting on the center rung as near the side rail as possible. The test load shall be applied for a period of one hour. Upon removal of the test load the fasteners attaching the rung to the side rail shall show no evidence of failure. The ladder shall remain operational following the test.
1113.6.1.7 Release Mechanism Test
The release mechanism of retractable exit ladder devices shall operate with an average applied force of not more than 5 pounds (22.2 N) for hand-operated releasing mechanisms and an average applied force of not more than 25 pounds (111 N) for foot-pedal types of releasing mechanisms. For these tests, a force gauge shall be applied to the release mechanism, and the average of three consecutive readings shall be computed.
1113.6.1.8 Low Temperature Operation Test
Representative samples of the exit ladder devices shall be subjected to a temperature of -40°C in an environmental chamber for a period of 24 hours. The release mechanism shall be operated immediately upon removal from the chamber. The ladder device shall function as intended without any restriction of operation.
Upcodes Diagrams
Related Code Sections
1113.6.1 Construction Requirements for Existing Buildings, Exit Ladder Devices
This standard for exit ladder devices is applicable where such devices are permitted by the building official for installation on existing apartment ...
1113.6.1 Construction Requirements for Existing Buildings, Exit Ladder Devices
This standard for exit ladder devices is applicable where such devices are permitted by the building official for installation on existing apartment ...
1113.6.1 Construction Requirements for Existing Buildings, Exit Ladder Devices
This standard for exit ladder devices is applicable where such devices are permitted by the building official for installation on existing apartment ...
313.6.1 Provisions for All Compliance Methods, Exit Ladder Devices
This standard for exit ladder devices is applicable where such devices are permitted by the building official for installation on existing apartment ...
313.6.1 Provisions for All Compliance Methods, Exit Ladder Devices
This standard for exit ladder devices is applicable where such devices are permitted by the building official for installation on existing apartment ...