• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

Section 1017 Exit Access Travel Distance

Building Code 2018 of Illinois > 10 Means of Egress > 1017 Exit Access Travel Distance
JUMP TO FULL CODE CHAPTER

1017.1 General

CALCULATE P
P Premium Feature

This feature is included in premium subscriptions only. Click below to start a free trial.

Try 2 Weeks Free
CALCULATE
Calculate code sheet portions referencing this topic.
Travel distance within the exit access portion of the means of egress system shall be in accordance with this section.

1017.2 Limitations

ILLUSTRATION
CALCULATE P
P Premium Feature

This feature is included in premium subscriptions only. Click below to start a free trial.

Try 2 Weeks Free
CALCULATE
Calculate code sheet portions referencing this topic.
Exit access travel distance shall not exceed the values given in Table 1017.2.
TABLE 1017.2
EXIT ACCESS TRAVEL DISTANCEa
OCCUPANCY WITHOUT SPRINKLER
SYSTEM
(feet)
WITH SPRINKLER
SYSTEM
(feet)
A, E, F-1, M, R, S-1 200e 250b
I-1 Not Permitted 250b
B 200 300c
F-2, S-2, U 300 400c
H-1 Not Permitted 75d
H-2 Not Permitted 100d
H-3 Not Permitted 150d
H-4 Not Permitted 175d
H-5 Not Permitted 200c
I-2, I-3 Not Permitted 200c
I-4 150 200c
For SI: 1 foot = 304.8 mm.
  1. See the following sections for modifications to exit access travel distance requirements:
    Section 402.8: For the distance limitation in malls.
    Section 404.9: For the distance limitation through an atrium space.
    Section 407.4: For the distance limitation in Group I-2.
    Sections 408.6.1 and 408.8.1: For the distance limitations in Group I-3.
    Section 411.3: For the distance limitation in special amusement buildings.
    Section 412.6: For the distance limitations in aircraft manufacturing facilities.
    Section 1006.2.2.2: For the distance limitation in refrigeration machinery rooms.
    Section 1006.2.2.3: For the distance limitation in refrigerated rooms and spaces.
    Section 1006.3.3: For buildings with one exit.
    Section 1017.2.2: For increased distance limitation in Groups F-1 and S-1.
    Section 1029.7: For increased limitation in assembly seating.
    Section 3103.4: For temporary structures.
    Section 3104.9: For pedestrian walkways.
  2. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. See Section 903 for occupancies where automatic sprinkler systems are permitted in accordance with Section 903.3.1.2.
  3. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  4. Group H occupancies equipped throughout with an automatic sprinkler system in accordance with Section 903.2.5.1.
  5. Group R-3 and R-4 buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.3. See Section 903.2.8 for occupancies where automatic sprinkler systems are permitted in accordance with Section 903.3.1.3.

1017.2.1 Exterior Egress Balcony Increase

Exit access travel distances specified in Table 1017.2 shall be increased up to an additional 100 feet (30 480 mm) provided that the last portion of the exit access leading to the exit occurs on an exterior egress balcony constructed in accordance with Section 1021. The length of such balcony shall be not less than the amount of the increase taken.

1017.2.2 Groups F-1 and S-1 Increase

The maximum exit access travel distance shall be 400 feet (122 m) in Group F-1 or S-1 occupancies where all of the following conditions are met:
  1. The portion of the building classified as Group F-1 or S-1 is limited to one story in height.
  2. The minimum height from the finished floor to the bottom of the ceiling or roof slab or deck is 24 feet (7315 mm).
  3. The building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.

1017.3 Measurement

Exit access travel distance shall be measured from the most remote point of each room, area or space along the natural and unobstructed path of horizontal and vertical egress travel to the entrance to an exit.
Exception: In open parking garages, exit access travel distance is permitted to be measured to the closest riser of an exit access stairway or the closest slope of an exit access ramp.

1017.3.1 Exit Access Stairways and Ramps

Travel distance on exit access stairways or ramps shall be included in the exit access travel distance measurement. The measurement along stairways shall be made on a plane parallel and tangent to the stair tread nosings in the center of the stair and landings. The measurement along ramps shall be made on the walking surface in the center of the ramp and landings.

Related Code Sections


Section 1017 Means of Egress, Exit Access Travel Distance
Travel distance within the exit access portion of the means of egress system shall be in accordance with this section ...
Building Code 2018 of Illinois > 10 Means of Egress > 1017 Exit Access Travel Distance
Section 1017 Means of Egress, Exit Access Travel Distance
Travel distance within the exit access portion of the means of egress system shall be in accordance with this section ...
Building Code 2021 of Illinois > 10 Means of Egress > 1017 Exit Access Travel Distance
404.9 Special Detailed Requirements Based on Occupancy and Use, Exit Access Travel Distance
Exit access travel distance for areas open to an atrium shall comply with the requirements of this section ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 404 Atriums > 404.9 Exit Access Travel Distance
404.9 Special Detailed Requirements Based on Occupancy and Use, Exit Access Travel Distance
Exit access travel distance for areas open to an atrium shall comply with the requirements of Section 1017 ...
Building Code 2021 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 404 Atriums > 404.9 Exit Access Travel Distance
407.5.2 Special Detailed Requirements Based on Occupancy and Use, Exit Access Travel Distance
The distance of travel from any point in a smoke compartment to a smoke barrier door shall be not greater than 200 feet (60 960 mm) ...
Building Code 2021 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 407 Group I-2 > 407.5 Smoke Barriers > 407.5.2 Exit Access Travel Distance
Help Contact Us Privacy Terms
Code Compare
Code Compare
Highlight differences between any two building codes.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING