13.2.3.4.1
Where an existing standpipe system, including yard piping and fire department connection, is modified, the new piping shall be independently tested in accordance with 11.4.1 of NFPA 14. [14:11.4.7.1]
13.2.3.4.2
Modifications that cannot be isolated, such as new valves or the point of connection for new piping, shall not require testing in excess of system static pressure. [14:11.4.7.2]
Upcodes Diagrams

Related Code Sections

13.2.3.4 Fire Protection Systems, Existing Systems
Where an existing standpipe system, including yard piping and fire department connection, is modified, the new piping shall be independently tested ...
13.2.3.4 Fire Protection Systems, Existing Systems
Where an existing standpipe system, including yard piping and fire department connection, is modified, the new piping shall be independently tested ...
401.3 Gas Piping Installations, Modifications to Existing Systems
In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter ...
401.3 Gas Piping Installations, Modifications to Existing Systems
In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter ...
808.2 Alterations—Level 2, Altered Existing Systems
In mechanically ventilated spaces, existing mechanical ventilation systems that are altered, reconfigured, or extended shall provide not less than 5 ...