1103.6.2 Existing Helistops and Heliports
Related Code Sections
1103.6.2 Construction Requirements for Existing Buildings, Existing Helistops and Heliports
Existing buildings with a rooftop helistop or heliport located more than 30 feet (9144 mm) above the lowest level of fire department access ...
2018 Philadelphia Fire Code > 11 Construction Requirements for Existing Buildings > 1103 Fire Safety Requirements for Existing Buildings > 1103.6 Standpipes > 1103.6.2 Existing Helistops and Heliports
Section 2007 Aviation Facilities, Helistops and Heliports
Helistops and heliports shall be maintained in accordance with Sections 2007.2 through 2007.8. Helistops and heliports on buildings shall ...
412.7 Special Detailed Requirements Based on Occupancy and Use, Heliports and Helistops
Heliports and helistops shall be permitted to be erected on buildings or other locations where they are constructed in accordance with Sections ...
2018 Philadelphia Building Code > 4 Special Detailed Requirements Based on Occupancy and Use > 412 Aircraft-Related Occupancies > 412.7 Heliports and Helistops
905.3.6 Fire Protection and Life Safety Systems, Helistops and Heliports
Buildings with a rooftop helistop or heliport shall be equipped with a Class I or III standpipe system extended to the roof level on which ...
2018 Philadelphia Building Code > 9 Fire Protection and Life Safety Systems > 905 Standpipe Systems > 905.3 Required Installations > 905.3.6 Helistops and Heliports
905.3.6 Fire Protection and Life Safety Systems, Helistops and Heliports
Buildings with a rooftop helistop or heliport shall be equipped with a Class I or III standpipe system extended to the roof level on which ...
2018 Philadelphia Fire Code > 9 Fire Protection and Life Safety Systems > 905 Standpipe Systems > 905.3 Required Installations > 905.3.6 Helistops and Heliports