506.3.12 Exhaust Outlets Serving Type I Hoods

NYC Mechanical Code 2014 > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.12 Exhaust Outlets Serving Type I Hoods
JUMP TO FULL CODE CHAPTER
Exhaust outlets for grease ducts serving Type I hoods shall conform to the requirements of Sections 506.3.12.1 through 506.3.12.3.

506.3.12.1 Termination Above the Roof

Exhaust outlets that terminate above the roof shall have the discharge opening located not less than 40 inches (1016 mm) above the roof surface. The exhaust flow shall be directed away from the surface of the roof.

506.3.12.2 Termination Through an Exterior Wall

Exhaust outlets shall be permitted to terminate through exterior walls where the smoke, grease, gases, vapors and odors in the discharge from such terminations do not create a public nuisance or a fire hazard. Such terminations shall not be located where protected openings are required by the New York City Building Code. Other exterior openings shall not be located within 3 feet (914 mm) of such terminations.

506.3.12.3 Termination Location

Exhaust outlets shall be located not less than 10 feet (3048 mm) horizontally from parts of the same or contiguous buildings, adjacent buildings and adjacent property lines and shall be located not less than 10 feet (3048 mm) above the adjoining grade level. Exhaust outlets shall be located not less than 10 feet (3048 mm) horizontally from and not less than 3 feet (914 mm) above air intake openings into any building.

Exception: Exhaust outlets shall terminate not less than 5 feet (1524 mm) from parts of the same or contiguous building, an adjacent building, adjacent property line and air intake openings into a building where air from the exhaust outlet discharges away from such locations.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


506.3.12 Exhaust Systems, Exhaust Outlets Serving Type I Hoods
Exhaust outlets for grease ducts serving Type I hoods shall conform to the requirements of Sections 506.3.12.1 through 506.3.12.3 ...
NYC Mechanical Code 2014 > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.12 Exhaust Outlets Serving Type I Hoods
506.3.12 Exhaust Systems, Exhaust Outlets Serving Type I Hoods
Exhaust outlets for grease ducts serving Type I hoods shall conform to the requirements of Sections 506.3.12.1 through 506.3.12.3 ...
NYC Mechanical Code 2008 > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.12 Exhaust Outlets Serving Type I Hoods
506.3.12.2 Exhaust Systems, Termination Through an Exterior Wall
Exhaust outlets shall be permitted to terminate through exterior walls where the smoke, grease, gases, vapors and odors in the discharge from ...
NYC Mechanical Code 2014 > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.12 Exhaust Outlets Serving Type I Hoods > 506.3.12.2 Termination Through an Exterior Wall
506.5.5 Exhaust Systems, Termination Location
The outlet of exhaust equipment serving Type I hoods, shall be in accordance with Section 506.3.12.3. Exception: The minimum horizontal ...
NYC Mechanical Code 2008 > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.5 Exhaust Equipment > 506.5.5 Termination Location
506.5.5 Exhaust Systems, Termination Location
The outlet of exhaust equipment serving Type I hoods, shall be in accordance with Section 506.3.12. Exception: The minimum horizontal distance ...
NYC Mechanical Code 2014 > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.5 Exhaust Equipment > 506.5.5 Termination Location
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US