506.5.6 Exhaust Fan Operation
Go To Full Code Chapter
The operation of the exhaust fan shall be in accordance with the following requirements:
- The hood exhaust fan(s) shall continue to operate after the extinguishing system has been activated unless fan shutdown is required by a listed component of the ventilation system or by the design of the extinguishing system.
- The hood exhaust fan shall not be required to start automatically upon activation of the extinguishing system if the exhaust fan and all cooking equipment served by the fan have previously been shut down.
- The cooking appliances shall be interlocked with the exhaust hood system to prevent appliance operation when the exhaust hood system is not operating.
Related Code Sections
506.5.6 Exhaust Systems, Exhaust Fan Operation
The operation of the exhaust fan shall be in accordance with the following requirements: The hood exhaust fan(s) shall continue to operate after ...
506.5.6 Exhaust Systems, Exhaust Fan Operation
The operation of the exhaust fan shall be in accordance with the following requirements: The hood exhaust fan(s) shall continue to operate after ...
506.5.6 Exhaust Systems, Exhaust Fan Operation
The operation of the exhaust fan shall be in accordance with the following requirements: The hood exhaust fan(s) shall continue to operate after ...
507.2.1.1 Exhaust Systems, Operation
Type I hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation ...
504.8 Exhaust Systems, Common Exhaust Systems for Clothes Dryers Located in Multistory Structures
is required per the New York City Building Code. Exhaust fan operation shall be monitored in an approved location and shall initiate an audible or visual ...