• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

910.4.2 Exhaust Fan Construction

Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 910 Smoke and Heat Removal > 910.4 Mechanical Smoke Removal Systems > 910.4.2 Exhaust Fan Construction
JUMP TO FULL CODE CHAPTER
Exhaust fans that are part of a mechanical smoke removal system shall be rated for operation at 221°F (105°C). Exhaust fan motors shall be located outside of the exhaust fan air stream.

Related Code Sections


910.4.2 Fire Protection and Life Safety Systems, Exhaust Fan Construction
Exhaust fans that are part of a mechanical smoke removal system shall be rated for operation at 221°F (105°C). Exhaust fan motors shall be located ...
Building Code 2021 of Illinois > 9 Fire Protection and Life Safety Systems > 910 Smoke and Heat Removal > 910.4 Mechanical Smoke Removal Systems > 910.4.2 Exhaust Fan Construction
910.4.2 Fire Protection and Life Safety Systems, Exhaust Fan Construction
Exhaust fans that are part of a mechanical smoke removal system shall be rated for operation at 221°F (105°C). Exhaust fan motors shall be located ...
Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 910 Smoke and Heat Removal > 910.4 Mechanical Smoke Removal Systems > 910.4.2 Exhaust Fan Construction
909.10.1 Fire Protection and Life Safety Systems, Exhaust Fans
Components of exhaust fans shall be rated and certified by the manufacturer for the probable temperature rise to which the components will be exposed ...
Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 909 Smoke Control Systems > 909.10 Equipment > 909.10.1 Exhaust Fans
909.10.1 Fire Protection and Life Safety Systems, Exhaust Fans
Components of exhaust fans shall be rated and certified by the manufacturer for the probable temperature rise to which the components will be exposed ...
Building Code 2021 of Illinois > 9 Fire Protection and Life Safety Systems > 909 Smoke Control Systems > 909.10 Equipment > 909.10.1 Exhaust Fans
C403.8 [CE] Commercial Energy Efficiency, Fans and Fan Controls
supply fans, exhaust fans, return/relief fans, and fan-powered terminal units associated with systems providing heating or cooling capability. Single ...
2018 Illinois Energy Conservation Code Standards for Privately Funded Commercial Facilities and Standards for Residential Buildings > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.8 Fans and Fan Controls
Help Contact Us Privacy Terms
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING