Domestic cooking exhaust equipment shall discharge to the outdoors through a duct. The duct shall have a smooth interior surface, shall be airtight, shall be equipped with a backdraft damper and shall be independent of all other exhaust systems. Ducts serving domestic cooking exhaust equipment shall not terminate in an attic or crawl space or areas inside the building.
Exception: Where installed in accordance with the manufacturer's instructions, and where mechanical or natural ventilation is otherwise provided, listed and labeled ductless range hoods shall not be required to discharge to the outdoors.

Related Code Sections

501.3 Exhaust Systems, Exhaust Discharge
The air removed by every mechanical exhaust system shall be discharged outdoors at a point where it will not cause a public nuisance and not less ...
501.3 Exhaust Systems, Exhaust Discharge
The air removed by every mechanical exhaust system shall be discharged outdoors at a point where it will not cause a public nuisance and not less ...
501.3 Exhaust Systems, Exhaust Discharge
The air removed by every mechanical exhaust system shall be discharged outdoors at a point where it will not cause a public nuisance and not less ...
M1503.3 Exhaust Systems, Exhaust Discharge
Domestic cooking exhaust equipment shall discharge to the outdoors through a duct. The duct shall have a smooth interior surface, shall be airtight ...
502.11.1 Exhaust Systems, Projectors With an Exhaust Discharge
Projectors equipped with an exhaust discharge shall be directly connected to a mechanical exhaust system. The exhaust system shall operate ...