[F] 414.5.2.1 Exempt Applications
JUMP TO FULL CODE CHAPTER
Emergency or standby power is not required for the mechanical ventilation systems provided for any of the following:
- Storage of Class IB and IC flammable and combustible liquids in closed containers not exceeding 6.5 gallons (25 L) capacity.
- Storage of Class 1 and 2 oxidizers.
- Storage of Class II, III, IV and V organic peroxides.
- Storage of asphyxiant, irritant and radioactive gases.
Related Code Sections
414.5.2.1 Special Detailed Requirements Based on Occupancy and Use, Exempt Applications
Emergency or standby power is not required for the mechanical ventilation systems provided for any of the following: Storage of Class IB and IC ...
Building Code 2021 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 414 Hazardous Materials > 414.5 Inside Storage, Dispensing and Use > 414.5.2 Emergency or Standby Power > 414.5.2.1 Exempt Applications
414.5.2.1 Special Detailed Requirements Based on Occupancy and Use, Exempt Applications
Emergency or standby power is not required for the mechanical ventilation systems provided for any of the following: Storage of Class IB and IC ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 414 Hazardous Materials > 414.5 Inside Storage, Dispensing and Use > 414.5.2 Emergency or Standby Power > 414.5.2.1 Exempt Applications
233.6.5.7 Scoping Requirements, Exemption
Dwelling units consisting of two stories are exempt from requirements for adaptability, as defined herein, if the required proportion of adaptable ...
2018 Illinois Accessibility Code > 2 Scoping Requirements > 233 Residential Facilities > 233.6 Multi-Story Housing > 233.6.5 Adaptable Dwelling Units > 233.6.5.7 Exemption
9.4.1.4 Lighting, Exterior Lighting Control
Lighting for exterior applications not exempted in Section 9.1 shall meet the following requirements: Lighting shall be controlled by a device ...
Energy Standard for Buildings Except Low-Rise Residential Buildings 2016 of Illinois > 9 Lighting > 9.4 Mandatory Provisions > 9.4.1 Lighting Control > 9.4.1.4 Exterior Lighting Control
903.3.1.1.1 Fire Protection and Life Safety Systems, Exempt Locations
from a room merely because it is damp, of fire-resistance-rated construction or contains electrical equipment. A room where the application of water ...
Building Code 2021 of Illinois > 9 Fire Protection and Life Safety Systems > 903 Automatic Sprinkler Systems > 903.3 Installation Requirements > 903.3.1 Standards > 903.3.1.1 NFPA 13 Sprinkler Systems > 903.3.1.1.1 Exempt Locations