// CODE SNIPPET
A.6.5 Example 5: Calculating Pressure Drops Due to Temperature Changes
JUMP TO FULL CODE CHAPTER
A test piping system is installed on a warm
autumn afternoon when the temperature is 70°F (21°C). In
accordance with local custom, the new piping system is subjected
to an air pressure test at 20 psig (138 kPa). Overnight,
the temperature drops and when the inspector shows up first
thing in the morning the temperature is 40°F (4°C).
If the volume of the piping system is unchanged, then the formula based on Boyle's and Charles' Jaw for determining the new pressure at a reduced temperature is as follows:
Therefore, the gauge could be expected to register 18 psig (124 kPa) when the ambient temperature is 40°F (4°C).
If the volume of the piping system is unchanged, then the formula based on Boyle's and Charles' Jaw for determining the new pressure at a reduced temperature is as follows:
where: | ||
T1 | = | Initial temperature, absolute (T1 + 459) |
T2 | = | Final temperature, absolute (T2 + 459) |
P1 | = | Initial pressure, psia (P1 + 14.7) |
P2 | = | Final pressure, psia (P2 + 14.7) |
P2 | = | 32.7 - 14.7 |
P2 | = | 18 psig |
Therefore, the gauge could be expected to register 18 psig (124 kPa) when the ambient temperature is 40°F (4°C).
Related Code Sections
A.6.5 Sizing and Capacities of Gas Piping, Example 5: Calculating Pressure Drops Due to Temperature Changes
system is subjected
to an air pressure test at 20 psig (138 kPa). Overnight,
the temperature drops and when the inspector shows up first
thing ...
2015 Michigan Residential Code > A Sizing and Capacities of Gas Piping > A.6 Examples of Piping System Design and Sizing > A.6.5 Example 5: Calculating Pressure Drops Due to Temperature Changes
E103.2.2 Sizing of Water Piping System,
Static pressure loss or gain (due to head) is computed at 0.433 psi per foot (9.8 kPa/m) of elevation change.
Example: Assume that the highest ...
2015 Michigan Plumbing Code > E Sizing of Water Piping System > E103 Selection of Pipe Size > E103.2 Pipe Sizing > E103.2.2
AP103.2.2 Sizing of Water Piping System,
and Section
604.3 of the International Plumbing Code.
Static pressure loss or gain (due to head) is computed
at 0.433 psi per foot (9.8 kPa/m ...
2015 Michigan Residential Code > P Sizing of Water Piping System > AP103 Selection of Pipe Size > AP103.2 Pipe Sizing > AP103.2.2
A.3.4 Sizing and Capacities of Gas Piping, Pressure Drop Per 100 Feet Method
). For each piping segment, calculate the pressure drop based on pipe size, length as a percentage of 100 feet (30 480 mm ...
2015 Michigan Residential Code > A Sizing and Capacities of Gas Piping > A.3 Use of Capacity Tables > A.3.4 Pressure Drop Per 100 Feet Method
M2105.28 Hydronic Piping, Testing
to the calculated design values. If actual flow rate
or pressure drop values differ from calculated design values
by more than 10 percent, the cause shall ...
2015 Michigan Residential Code > 21 Hydronic Piping > M2105 Ground-Source Heat-Pump System Loop Piping > M2105.28 Testing